Plan Review Notes
Plan Review Notes For Permit 09120347
Permit Number 09120347
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-26 22:32:15*****DENIED*****
  
 1. THE CORRECT ADDRESS (8101 OKEECHOBEE BLVD., WEST
 PALM BEACH) SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET AND ANY OTHER DOCUMENTS/SUBMITTALS
 WHICH REFERENCE THIS PROJECT SITE. INCORRECT NUMERICAL
 ALSO SHOWN ON SHEET 3 IN THE INFORMATION FOR THE
 HYDRAULICALLY CALCULATED SYSTEM.
  
 2. AMEND SUPPLY FLOW TEST DATA TO REFLECT THAT THE TEST
 WAS CONDUCTED BY WEST PALM BEACH FIRE RESCUE.
  
 3. AMEND PAGES 1 AND 2 OF THE HYDRAULIC OVERVIEW
 SUBMITTALS TO REFLECT THE CORRECT NUMERICAL ADDRESS,
 THE CORRECT CITY, AND THE CORRECT AUTHORITY HAVING
 JURISDICTION (AHJ).
  
 4. IN THE SPRINKLER LEGEND ON SHEET 1 OF 3, EXPLAIN THE
 DIFFERENT DEGREE LISTINGS (200, 155) FOR THE TYCO) 3/4"
 EXTENDED COVERAGE PENDANT.
  
 5. DUE TO THE SIMILIARITY IN THE CIRCULAR DEVICES, IT
 IS DIFFICULT TO DETERMINE THE 9 (SHEET 1) AND 5 (SHEET
 2) TYCO 1/2" BRASS UPRIGHT SPRINKLERS.
  
 6. ADD TO GENERAL NOTES: " KNOX LOCKING CAPS SHALL BE
 REQUIRED FOR THE FIRE DEPARTMENT CONNECTION (FDC). "
 FOR APPLICATIONS CONTACT WEST PALM BEACH FIRE RESCUE AT
 561-804-4724
  
 7. SPRINKLER PROTECTION FOR THE CANOPY TO BE DETERMINED
 BY WEST PALM BEACH FIRE PREVENTION UPON
 VERIFICATION/DOCUMENTATION OF NONCOMBUSTIBLE OR LIMITED
 COMBUSTIBLE CONSTRUCTION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722