2010-02-01 16:59:03 | REVISION TO 09100241 |
| |
| REVISED SHEETS A2.1, A3.1, A4.1, A5.2 AND A5.3 ARE OK. |
| |
| STORM PANEL SUBMITTALS ARE DENIED BY BUILDING. |
| |
| 1) THE STORM PANEL INSTALLATION SCHEDULE IS NOT |
| COMPLETED. THE WALL PRESSURES THAT ARE SPECIFIED ON THE |
| FORM ARE FOR OPENINGS OF 20 SQUARE FEET. |
| |
| 2) THE WINDOW SIZES ON THE STORM PANEL SCHEDULE DO NOT |
| CORRESPOND WITH THE ONES ON THE PLANS (A2.1). PLEASE |
| CORRECT. |
| |
| 3) THE LETTER TO THE BUILDING OFFICIAL REQUESTING THE |
| USE OF STORM PANELS IS REQUIRED TO BE FROM THE BUSINESS |
| OWNER. IN ADDITION TO THE STORE OWNER, SPECIFY AN |
| ALTERNATE PERSON THAT WILL BE RESPONSIBLE FOR |
| INSTALLING THE STORM PANELS IF THE OWNER IS NOT |
| AVAILABLE. |
| |
| 4) THE LETTER INDICATES THAT THE STORM PANELS WILL BE |
| STORED IN THE ATTIC. PLEASE SPECIFY THE SIZE OF THE |
| ATTIC ACCESS OPENING. |
| |
| 5) THE PRODUCT APPROVAL DRAWINGS THAT WERE SUBMITTED |
| (08-142) ARE FOR 24GA. STEEL PANELS, WHICH WILL ADD A |
| SUBSTANTIAL LIVE LOAD TO THE ATTIC. SUBMIT DETAILS FOR |
| THE STRUCTURE OF THE CEILING SHOWING THAT THE LOADS |
| WILL BE SAFELY SUPPORTED. |
| |
| 6) THE LETTER ALSO NEEDS TO STATE THAT THE TOOLS AND |
| EQUIPMENT (SUCH AS LADDERS) REQUIRED FOR INSTALLING THE |
| PANELS WILL ALSO BE STORED ON SITE. |
| |
| 7) PLEASE CLARIFY THE PURPOSE OF THE FLEMING STEEL DOOR |
| AND FRAME UL FOLLOW-UP INFORMATION THAT WAS ATTACHED TO |
| THE STORM PANEL SUBMITTAL. |
| |