2010-02-01 16:59:03REVISION TO 09100241
  
 REVISED SHEETS A2.1, A3.1, A4.1, A5.2 AND A5.3 ARE OK.
  
 STORM PANEL SUBMITTALS ARE DENIED BY BUILDING.
  
 1) THE STORM PANEL INSTALLATION SCHEDULE IS NOT
 COMPLETED. THE WALL PRESSURES THAT ARE SPECIFIED ON THE
 FORM ARE FOR OPENINGS OF 20 SQUARE FEET.
  
 2) THE WINDOW SIZES ON THE STORM PANEL SCHEDULE DO NOT
 CORRESPOND WITH THE ONES ON THE PLANS (A2.1). PLEASE
 CORRECT.
  
 3) THE LETTER TO THE BUILDING OFFICIAL REQUESTING THE
 USE OF STORM PANELS IS REQUIRED TO BE FROM THE BUSINESS
 OWNER. IN ADDITION TO THE STORE OWNER, SPECIFY AN
 ALTERNATE PERSON THAT WILL BE RESPONSIBLE FOR
 INSTALLING THE STORM PANELS IF THE OWNER IS NOT
 AVAILABLE.
  
 4) THE LETTER INDICATES THAT THE STORM PANELS WILL BE
 STORED IN THE ATTIC. PLEASE SPECIFY THE SIZE OF THE
 ATTIC ACCESS OPENING.
  
 5) THE PRODUCT APPROVAL DRAWINGS THAT WERE SUBMITTED
 (08-142) ARE FOR 24GA. STEEL PANELS, WHICH WILL ADD A
 SUBSTANTIAL LIVE LOAD TO THE ATTIC. SUBMIT DETAILS FOR
 THE STRUCTURE OF THE CEILING SHOWING THAT THE LOADS
 WILL BE SAFELY SUPPORTED.
  
 6) THE LETTER ALSO NEEDS TO STATE THAT THE TOOLS AND
 EQUIPMENT (SUCH AS LADDERS) REQUIRED FOR INSTALLING THE
 PANELS WILL ALSO BE STORED ON SITE.
  
 7) PLEASE CLARIFY THE PURPOSE OF THE FLEMING STEEL DOOR
 AND FRAME UL FOLLOW-UP INFORMATION THAT WAS ATTACHED TO
 THE STORM PANEL SUBMITTAL.
  