2009-12-28 12:24:37 | REVISION TO 09100241 | | | | DENIED BY BUILDING | | | | 1) THE REVISED PLANS DO NOT SHOW COMPLIANCE WITH | | ACCESSIBILITY REQUIREMENTS FOR FIXED SEATING AND | | TABLES, COUNTER-TOP HEIGHTS AND REQUIRED CLEAR FLOOR | | SPACE. SHOW COMPLIANCE WITH FBC 11-4.32, 4.33, 5.1 AND | | 5.2. | | | | 2) REVISE THE HANDRAIL DETAIL IN SECTION E ON SHEET | | A2.1 TO COMPLY WITH FBC 11-4.9.4(3) WHICH REQUIRES THE | | CLEAR SPACE BETWEEN HANDRAILS AND THE WALL TO BE | | 1-1/2". THIS IS AN ABSOLUTE DIMENSION. IN THE DETAIL | | THIS MEASUREMENT IS SHOWN TO THE MOUNTING BRACKET | | FLANGE, NOT THE WALL. | | | | 3) IN SECTION B ON SHEET A2.1 A PORTION OF THE TEXT HAS | | BEEN DELETED. PLEASE CORRECT. | | | | 4) ON THE CEILING PLAN ON SHEET A3.1 THERE SHOULD BE AN | | ADDITIONAL DIRECTIONAL EXIT SIGN AT THE TOP OF THE | | STAIRS SHOWING THE DIRECTION OF EGRESS TO THE EXIT | | DOORS. FBC 1006.3.8 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|