2009-12-21 13:58:24REVIEW #: 1ST
 ACTION: **PROVISO**
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M2.2: PLAN SHOWS DUCTS PENETRATING RATED WALLS
 WITHOUT PROTECTION. EXAMPLE: 32X14 AND 75X14 DUCTS
 ENTERING SUITE 220. PLEASE COORDINATE ALL RATED WALL
 LOCATIONS WITH ARCHITECTURAL PLANS AND REVISE
 MECHANICAL PLANS (PRIOR TO INSPECTION) TO SHOW ALL
 PENETRATIONS OF RATED ASSEMBLIES PROTECTED IN
 ACCORDANCE WITH FBC-M 607.8.
  
 2. PAGE M2.2: FILING ROOM 227 IS A SEPARATE FIRE AREA
 AND CAN NOT BE PART OF THE RETURN AIR PLENUM IN
 ACCORDANCE WITH FBC-M 602.1.
  