Plan Review Notes
Plan Review Notes For Permit 09120243
Permit Number 09120243
Review Stop B
Sequence Number 4
Notes
Date Text
2011-04-14 10:19:16MASTER PLAN (MODEL B) FOR NEW SINGLE FAMILY RESIDENCE
 (R3), BUILDING REVIEW THIRD CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT
 COMMENT. NOT ADDRESSED AT ALL. NEED THE ENERGY
 CALCULATIONS FOR WORST CASE SCENARIO WHEN APPLYING FOR
 A MASTER PERMIT ).
  
  
 ****REVIEW IN PROGRESS*** REVIEW STOPPED FEES ARE NOT
 PAID. CONTRACTOR WAS NOTIFIED BY LUIS MARTINEZ
 REGARDING THE FEES.
  
  
  
  
 3- ALL DRAWINGS HAVE THE LOT 42 ON THE TITLE BLOCK.
 DELETE AS REQUIRED.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS
 SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT
 NOA.
  
 B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED
 EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE
 REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE.
  
 C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON
 JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR
 FUTURE SUBMITTAL AFTER THIS DATE.
  
 D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA
 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10
 WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS
 GOING TO BE USED.
  
 E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 H) STORM SHUTTERS. COORDINATE WITH ITEM # 4D ABOVE. AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON
 SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR
 TYPE AND SPACING.
  
 I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF
 PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS
 APPLIES TO NOA'S NO SUBMITTED YET.
  
 6- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO
 EXPOSURE "C" BUT THE DOORS AND WINDOWS DESIGN PRESSURES
 ON SHEETS A-3.0, A-4.0, A-5.0 AND A-7.0 WERE NOT
 CHANGED TO REFLECT EXPOSURE "C".
  
 7- TRUSS PACKAGE:
 A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO
 EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL
 TRUSSES ACCORDINGLY.
  
 B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION,
 INCLUDING THE ARCHITECT OF RECORD INFORMATION.
  
 C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT
 COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 8- REVISED SHEET A-2.0:
 A) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFIES 10
 MIL VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6
 MIL VAPOR BARRIER. REVISE AS REQUIRED TO MATCH.
  
 B) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE
 ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE NOTE REGARDING TRUSS ANCHORS. USING SIMPSON
 NOT USP, AND REFER TO CORRECT SHEET.
  
 9- SHEET A-7.0: CLARIFY NOTE ON FRONT ELEVATION
 REGARDING DECORATIVE LOUVER. THERE IS NOT LOUVER SHOWN
 ON THE ELEVATION.
  
 10- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS
 CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1.
  
 11- SHEET A-6.0:
 A) COORDINATE DETAIL 4/A-6.0 WITH FASTENERS SPECIFIED
 ON STRUCTURAL CONNECTOR SCHEDULE. REVISE TYPE OF
 FASTENERS TO MATCH.
  
 B) FASTENER SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED
 BECAUSE IT DOESN'T PROVIDE ANY UPLIFT. SEE SIMPSON
 CATALOG. REVISE AS REQUIRED AND COORDINATE DETAIL AND
 TRUSS ANCHOR SCHEDULE
  
 JULIO GOMEZ
 COMBINATION COMMERCIAL PLANS EXAMINER
 (561)805-6712