Plan Review Notes
Plan Review Notes For Permit 09120243
Permit Number 09120243
Review Stop E
Sequence Number 3
Notes
Date Text
2011-02-01 12:52:45PROVIDE INTERRUPTING (AIC) CURRENT RATING FOR THE
 ELECTRICAL SERVICE. NEC 110.9
 CORRECT NOTES TO REFLECT THE CURRENT ELECTRIC CODE:
 2008 NEC
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC
 250.94
 THREE RECEPTACLES REQUIRED IN TWO HALLWAYS. NEC 210.52
 (H)
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES. NEC 406.11
 AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE
 PROVIDED ON THE EXTERIOR SIDE OF THE SIDE ENTRANCE. NEC
 210.70 (A) (2) (B).
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH COMBINATION
 - TYPE AFCI'S. NEC 210.12 (B)
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved