2011-01-24 14:10:00 | MASTER PLAN (MODEL B) FOR NEW SINGLE FAMILY RESIDENCE |
| (R3), BUILDING REVIEW SECOND CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT |
| COMMENT. NOT ADDRESSED). |
| |
| 2- SHEET A/A1.0: LEAVE LOCATION MAP BOX IN BLANK. THIS |
| IS APPLICATION FOR MASTER NOT FOR A SPECIFIC LOT. |
| |
| 3- ALL DRAWINGS HAVE THE LOT 42 ON THE TITLE BLOCK. |
| DELETE AS REQUIRED. |
| |
| 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS |
| SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT |
| NOA. |
| |
| B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED |
| EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE |
| REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE. |
| |
| C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON |
| JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR |
| FUTURE SUBMITTAL AFTER THIS DATE. |
| |
| D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA |
| 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10 |
| WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS |
| GOING TO BE USED. |
| |
| E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS. (REPEAT |
| COMMENT). |
| |
| F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. (REPEAT |
| COMMENT). |
| |
| G) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT |
| COMMENT. NOT ADDRESSED). |
| |
| H) STORM SHUTTERS. COORDINATE WITH ITEM # 4D ABOVE. AND |
| PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON |
| SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR |
| TYPE AND SPACING. |
| |
| I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF |
| PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR. |
| (REPEAT COMMENT. NOT ADDRESSED). |
| |
| 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS |
| APPLIES TO NOA'S NO SUBMITTED YET. |
| |
| 6- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO |
| EXPOSURE "C" BUT THE DOORS AND WINDOWS DESIGN PRESSURES |
| ON SHEETS A-3.0, A-4.0, A-5.0 AND A-7.0 WERE NOT |
| CHANGED TO REFLECT EXPOSURE "C". |
| |
| 7- TRUSS PACKAGE: |
| A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO |
| EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL |
| TRUSSES ACCORDINGLY. |
| |
| B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION, |
| INCLUDING THE ARCHITECT OF RECORD INFORMATION. |
| |
| C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT |
| COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| |
| 8- REVISED SHEET A-2.0: |
| A) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFIES 10 |
| MIL VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6 |
| MIL VAPOR BARRIER. REVISE AS REQUIRED TO MATCH. |
| |
| B) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE |
| ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE. |
| |
| C) REVISE NOTE REGARDING TRUSS ANCHORS. USING SIMPSON |
| NOT USP, AND REFER TO CORRECT SHEET. |
| |
| 9- SHEET A-7.0: CLARIFY NOTE ON FRONT ELEVATION |
| REGARDING DECORATIVE LOUVER. THERE IS NOT LOUVER SHOWN |
| ON THE ELEVATION. |
| |
| 10- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS |
| CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1. |
| |
| 11- SHEET A-6.0: |
| A) COORDINATE DETAIL 4/A-6.0 WITH FASTENERS SPECIFIED |
| ON STRUCTURAL CONNECTOR SCHEDULE. REVISE TYPE OF |
| FASTENERS TO MATCH. |
| |
| B) FASTENER SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED |
| BECAUSE IT DOESN'T PROVIDE ANY UPLIFT. SEE SIMPSON |
| CATALOG. REVISE AS REQUIRED AND COORDINATE DETAIL AND |
| TRUSS ANCHOR SCHEDULE |
| |