Plan Review Notes
Plan Review Notes For Permit 09120243
Permit Number 09120243
Review Stop P
Sequence Number 1
Notes
Date Text
2009-12-22 15:55:29DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A1.0 INDICATES THE DESIGN TO BE PER FBC-2004.
 ALL PLANS SUBMITTED FOR PERMIT AFTER MARCH 1, 2009
 SHALL BE DESIGNED TO THE FBC-2007 EDITION WITH 2009
 SUPPLEMENTALS. PLEASE CORRECT CODE REFERENCES. SECTION
 106.1.1.
  
 2. ALL SHEETS DESIGNED BY AN ARCHITECT OR ENGINEER
 SHALL BE SIGNED, SEALED & DATED PER CHAPTERS 481 & 471
 OF THE FLORIDA STATUTES AND SECTION 106.1.
  
 3. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION. PLEASE INDICATE THE
 ADDRESS OF THE RESIDENCE ON THE TITLE BLOCK OF EACH
 SHEET. SECTION 106.1.1.
  
 4. SHT P2.01 GENERAL PLUMBING NOTES #7 INDICATES A
 1-1/4 INCH METER AND A 1-1/4 INCH WATER SERVICE WITH
 GATE VALVE AT THE HOUSE. PER TABLE 603.1 18 FIXTURE
 UNITS OR LESS ONLY REQUIRES A 5/8 INCH METER AND 3/4
 INCH WATER SERVICE. THE TOTAL FIXTURE UNITS FOR THE
 RESIDENCE IS ONLY 14. PLEASE CLARIFY IF THE METER AND
 GATE VALVE INDICATED AS WELL SUB-NOTES A THRU E ARE
 REQUIRED FOR THIS RESIDENCE.
  
 5. SHT P2.01 GENERAL PLUMBING NOTES #8 INDICATES AIR
 CHAMBERS AT EACH FIXTURE. AIR CHAMBERS ARE NOT APPROVED
 AND SHALL BE DELETED. PDI-WH 201.
  
 6. SHT P2.01 SANITARY RISER DIAGRAM. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH
 DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER. SECTION 406.3/P2718.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  