2010-01-06 10:35:42NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM.
 COORDINATE WITH THE HEATING AND COOLING CALCULATIONS
 REQUIRED BY SEC. N1100.AB.
  
 4- SHEET M2.01:
 A) UPDATE MECHANICAL NOTE #1. CURRENT CODE IS THE 2007
 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 B) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND
 COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS
 REQUIRED ON ITEM #2 ABOVE.
  
 C) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007
 FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION
 AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA
 SPECIFIED ON THE ARCHITECTURAL PLANS.
  
 5- PLANS NEED TO BE SIGNED AND SEALED BY THE
 PROFESSIONAL OF RECORD AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTE.
  