2009-12-22 11:22:44 
  
 APPLICATION #09120136 ELECTRICAL PLAN REVIEW
 1107 22ND STREET 12/22/09
 WEST PALM BEACH, FL.
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET A-1 ALL THE ???APPLICABLE CODES??? NOTED ARE
 FROM THE PREVIOUS CODE CYCLE, CORRECT SAME.
  
 2} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER 481.221(1)
 (B) FS.
  
 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 4} AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. 250.94, 2008 NEC.
  
 5} NOTE #4 IN THE ???GENERAL NOTES??? SHEET E2.01
 REFERENCES ARC FAULT PROTECTION FOR BEDROOMS. SEE
 210.12, 2008 NEC TO CORRECT THE NOTE.
  
 NOTE: CHANGE IN THE 2008 NEC AN INTERSYSTEM BONDING
 TERMINATION FOR CONNECTING INTERSYSTEM BONDING AND
 GROUNDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL
 BE PROVIDED EXTERNAL TO ENCLOSURES AT THE SERVICE
 EQUIPMENT AND AT THE DISCONNECTING MEANS FOR ANY
 ADDITIONAL BUILDINGS OR STRUCTURES. 250.94, 2008 NEC.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  