| APPLICATION #09120136 ELECTRICAL PLAN REVIEW |
| 1107 22ND STREET 12/22/09 |
| WEST PALM BEACH, FL. |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} SHEET A-1 ALL THE ???APPLICABLE CODES??? NOTED ARE |
| FROM THE PREVIOUS CODE CYCLE, CORRECT SAME. |
| |
| 2} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON |
| THE PLANS, MUST SIGN AND SEAL THE PLAN PER 481.221(1) |
| (B) FS. |
| |
| 3} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. |
| |
| 4} AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| STRUCTURES. 250.94, 2008 NEC. |
| |
| 5} NOTE #4 IN THE ???GENERAL NOTES??? SHEET E2.01 |
| REFERENCES ARC FAULT PROTECTION FOR BEDROOMS. SEE |
| 210.12, 2008 NEC TO CORRECT THE NOTE. |
| |
| NOTE: CHANGE IN THE 2008 NEC AN INTERSYSTEM BONDING |
| TERMINATION FOR CONNECTING INTERSYSTEM BONDING AND |
| GROUNDING CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL |
| BE PROVIDED EXTERNAL TO ENCLOSURES AT THE SERVICE |
| EQUIPMENT AND AT THE DISCONNECTING MEANS FOR ANY |
| ADDITIONAL BUILDINGS OR STRUCTURES. 250.94, 2008 NEC. |
| |
| |