2009-12-17 08:25:38 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS. |
| |
| 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| **NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| |
| 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| PAY IMPACT FEES. BRING BACK STAMPED PLANS AND COPY OF |
| PAID RECEIPT IF FEES ARE DUE. |
| |
| 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 4- DRAWINGS SUBMITTED ARE DESIGNED UNDER THE 2004 FBC. |
| ALL DRAWINGS NEED TO SPECIFY CURRENT CODE (2007 FLORIDA |
| RESIDENTIAL CODE WITH 2009 SUPPLEMENTS) AND CURRENT |
| EDITION OF THE REFERENCED STANDARDS. REVISE SHEETS |
| A/A1.0, A/2.01 AND S/3.01. |
| |
| 5- ALL PLANS NEED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OF RECORD. SEC. 481 FLORIDA STATUTE. |
| |
| 6- SHEET A/A1.0: |
| A) PROVIDE SITE PLAN FOR CURRENT HOUSE TO BE BUILT. |
| SPECIFY ALL LOT DIMENSIONS, BUILDING DIMENSIONS AND |
| SETBACKS. |
| |
| B) REVISE INFORMATION ON LOCATION MAP TO MATCH ACTUAL |
| HOUSE TO BE BUILT. |
| |
| 7- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF SHINGLES. |
| B) SINGLE HUNG WINDOWS. |
| C) WINDOW MULLIONS. AND SPECIFY MULLION SIZE AND |
| ANCHORS. |
| D) ENTRY DOOR. |
| E) REAR DOOR. |
| F) STORAGE DOUBLE DOORS. |
| G) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| H) STORM SHUTTERS. AND PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. ALSO, MARK ON SHUTTERS DRAWING SPECIFIC |
| MOUNTING CONDITION AND ANCHOR TYPE AND SPACING. |
| I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF |
| PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR. |
| |
| 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 9- PROVIDE 2 COPIES OF SOIL TEST REPORT. SEC. R401.4 OF |
| 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 10- SHEET A/2.01: SPECIFY SAFETY GLASS FOR WINDOW THAT |
| IS ADJACENT TO THE ENTRY DOOR. SEC. R308.4(6). |
| |
| 11- SHEET S/3.01: REVISE THE FLORIDA BUILDING CODE |
| DESIGN PARAMETERS. ACCORDING TO SEC. R301.2.1.4.3 OF |
| 2009 REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE |
| THIS HOUSE IS LOCATED ON EXPOSURE "C" NOT "B". NEED TO |
| REVISE THE EXPOSURE AND THE DESIGN PRESSURES SHOWN ON |
| SHEET A/3.01. |
| |
| 12- OWES $2727.14 FOR THE PERMIT FEE BALANCE. |
| |