Plan Review Notes For Permit 09120221 |
Permit Number |
09120221 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-12-15 14:21:01 | MECHANICAL PROVISO: MASTER SUITE, 14???X14??? MINIMUM | | TRANSFER GRILLE. | | PLEASE SEE SECTION 601.4(2) TRANSFER GRILLES SHALL USE | | 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF SUPPLY | | AIR) FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND | | USING AN UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | | | |
|