Plan Review Notes
Plan Review Notes For Permit 09120221
Permit Number 09120221
Review Stop M
Sequence Number 2
Notes
Date Text
2009-12-15 14:21:01MECHANICAL PROVISO: MASTER SUITE, 14???X14??? MINIMUM
 TRANSFER GRILLE.
 PLEASE SEE SECTION 601.4(2) TRANSFER GRILLES SHALL USE
 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF SUPPLY
 AIR) FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
  