2009-12-15 13:10:21PERMIT# 09080208
 REVISION# 09120221
 MECHANICAL:
  
 DENIED
  
 1) MASTER SUITE PLEASE SEE SECTION 601.4(2) TRANSFER
 GRILLES SHALL USE 50 SQUARE INCHES (OF GRILLE AREA) TO
 100 CFM (OF SUPPLY AIR) FOR SIZING THROUGH-THE-WALL
 TRANSFER GRILLES AND USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE. THE MATH INDICATES THE TRANSFER GRILLE WOULD
 BE TO SMALL,112 SQ INCHES WHEN 175 SQ INCHES WOULD JUST
 BALANCE THE SYSTEM.
  
 JIM WITMER C. B. O.