Plan Review Notes
Plan Review Notes For Permit 09120182
Permit Number 09120182
Review Stop B
Sequence Number 1
Notes
Date Text
2009-12-16 09:17:48****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE FBC*106, ARCHITECTURAL QUALITY PLANS DRAWN TO
 SCALE ARE REQUIRED. PROVIDE A FLOOR PLAN SHOWING
 PROPOSED IMPROVEMENT LOCATION , ROOM DESIGNATION.
 PHOTOGRAPHS CANNOT NOT BE USED IN LIEU OF PLANS.
  
 2. PROVIDE A STRUCTURAL DETAIL WHICH INCLUDES ALL
 DIMENSIONS, BUCK SPECIFICATION, CONNECTION INTO
 EXISTING.
  
 3. THE PRODUCT APPROVAL IS INCOMPLETE. PLEASE PROVIDE
 ALL SHEETS AS ALL PAGES ARE REQUIRED TO DEMONSTRATE
 CODE COMPLIANCE.
  
 4. PROVIDE A REASONABLE VALUE FOR THIS JOB WHICH
 INCLUDES VALUE OF ALL MATERIALS AND LABOR.
  
 5. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 IF THIS FALLS UNDER THE 25% EXCEPTION FBC EB 507.3,
 PROVIDE CALCULATIONS.
  
  
  
  
  