Plan Review Notes For Permit 09120164 |
Permit Number |
09120164 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-01-12 11:06:21 | ** PROVISO * | | | | * REVISE BEFORE FINALS. | | | | | | 1) NOTE: PLEASE PROVIDE COPY OF UNITY OF TITLE AS | | ELECTRICAL CROSSES THE PROPERTY LINES SHOWN ON PALM | | BEACH COUNTY PROPERTY APPRAISER WEB-SITE. | | | | 2) NOTE: SIGN CIRCUIT REQUIRED PER 600.5 ( 1200 VA MIN) | | | | 3) NOTE: ALL CONTINUOUS LOADS INCLUDING SIGN ABOVE ARE | | REQUIRED TO BE FIGURED AT 125%. | | 215.3, 230.42 ETC. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | |
|