2009-12-28 14:37:13*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS REVIEW (UNDER
 #09070059) STILL NEED TO BE ADDRESSED:
  
 3. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 4. PLEASE PROVIDE TRAVEL DISTANCE TO THE EXITS.
  
 5. SHOW THE LOCATION OF THE EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE REMODELED
 FLOOR PLAN.
  
 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7. SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OR CLASS II.
  
 8. ARE THE DEVICES SHOWN IN THE ELECTRICAL FLOOR PLAN
 (SHEET A03) SMOKE DETECTORS (SD) OR SMOKE ALARMS (SA) ?
 PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE TIED
 INTO A BUILDING'S FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW