Date |
Text |
2009-12-22 11:06:51 | ** DENIED 2ND ** |
| |
| MINIMUM DOCUMENTS FOR CODE COMPLIANCE HAS NOT ALL BEEN |
| SUBMITTED. |
| |
| 1) NOTE: THIS IS A CHANGE IN OCCUPANCY WHICH IS |
| REQUIRED TO MEET MINIMUMS UNDER THE EXISTING BUILDING |
| CODE, ELECTRICAL CODE AND ENERGY CODE. |
| PLEASE SUBMIT COMPLETED PLANS AND SUPPORTING DOCUMENTS. |
| PLEASE SEE EXISTING BUILDING CODE 2007 W/ 2009 |
| SUPPLEMENTS, SEE CHAPTER 9. |
| PLEASE SEE FBC 2007 W2009 SUPPLEMENTS FOR CHAPTER |
| 13.101.3 |
| CHANGES IN OCCUPANCY TO A HIGHER HAZARD ALSO REQUIRES |
| ALL ELECTRICAL TO MEET CURRENT ADOPTED CHAPTER 27 OF |
| THE FBC. |
| |
| 2) NOTE: PLEASE HAVE OWNER FILE FOR A UNITY OF TITLE |
| FOR THIS PROPERTY AND THE SEPARATE LEGAL PROPERTY TO |
| THE WEST WHICH IS 342 CONNISTON RD. BASED ON THE PALM |
| BEACH COUNTY PROPERTY APPRAISER OFFICE RECORD, MAPS, |
| AND PLANS THERE IS STRUCTURAL AND ELECTRICAL WHICH |
| CROSS THE PROPERTY LINE WHICH IS NOT PERMITTED. |
| |
| 3) NOTE: NEW RISER NOW INDICATES A TOTAL OF 525AMPS |
| WORTH OF SERVICE AND SERVICE ENTRANCE CONDUCTORS ONLY |
| RATED FOR 200AMPS. PLEASE SEE 240.4, 310.16 FOR MINIMUM |
| SIZING. |
| |
| 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS BASED ON MIXED |
| USE OCCUPANCY AS NOW STATED AND SHOWN ON PLANS. |
| PLEASE SEE NEC 220, MORE SPECIFICALLY 220.12, 220.14, |
| 220.42, 220.43, ETC. |
| PLEASE ALSO SEE 215.3, 230.42 FOR ALL CONTINUOUS LOADS |
| @125%. |
| PLEASE SEE 422.13 FOR ANY STORAGE TYPE WATER HEATERS |
| WHICH ALSO REQUIRED CONTINUOUS LOADS AT 125%. |
| |
| 5) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS |
| ALONG WITH LIGHTING PERFORMANCE CALCULATIONS. PLEASE |
| SEE FBC 13-101.3, 13-400, 13-103, 13-415.AB.5, |
| 13-415.AB.2.2 ETC |
| |
| 6) NOTE: PLEASE SHOW ALL MINIMUM CIRCUITING FOR NEW |
| OCCUPANCY BASED ON COMMERCIAL USE. ALL CIRCUITING IS TO |
| BE SHOWN ON PLANS AND NEEDS TO COORDINATE WITH |
| SUBMITTED PANEL SCHEDULE(S). |
| PANEL SCHEDULE MAY NOT ONLY STATE *RECEPTACLES OR |
| LIGHTING* IN GENERAL TERMS. CIRCUITS ARE TO BE SPECIFIC |
| TO ROOMS AND AREAS IN WHICH THEY FEED. ALPHA OR NUMERIC |
| DESIGNATIONS MAY BE USED. |
| 408.4, 220.12, 220.14, 220.18, 220.43, 220.44 ETC |
| |
| 7) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY |
| LIGHTING AND EXIT LIGHTS. THESE ARE REQUIRED TO BE |
| CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT IN ANY ONE |
| AREA. |
| |
| 8) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT. |
| PLEASE BE SURE TO INCLUDE MINIMUM BRANCH CIRCUIT LOAD. |
| |
| 9) NOTE: PLEASE SEE 210.62 FOR SHOW WINDOW RECEPTACLES |
| REQUIRED. PLEASE SEE 220.43 FOR REQUIRED LOAD IN LOAD |
| CALCULATIONS. |
| |
| 10) NOTE: PLANS INDICATE SMOKE DETECTORS HOWEVER NO |
| INFORMATION ON FIRE ALARM PANEL, LOCATION ETC IS SHOWN. |
| PLEASE COMPLETED PLANS IF THIS IS A REQUIRED SYSTEM. FS |
| 633 REQUIRES ANY REQUIRED SYSTEM DESIGN INTENT TO BE |
| SHOWN ON BASE PLANS EVEN WHEN FIRE ALARM PERMITS ARE |
| FILED UNDER SEPARATE PERMITS. IF THIS IS A REQUIRED |
| SYSTEM PLEASE BE SURE TO SEE FBC CHAPTER 11, 11-4.28.1, |
| .2 AND .3 FOR MINIMUM LEVELS FOR ADA COMPLIANCE. |
| |
| 11) NOTE: BATHROOM RECEPTACLES SHALL BE GFI/GFI |
| PROTECTED PER 210.8B |
| |
| 12) NOTE: EXTERIOR LIGHTING SHALL MEET CONTROLS UNDER |
| FBC 13-415.AB.1.4 |
| |
| 13) NOTE: EXTERIOR RECEPTACLE ON PLANS IS REQUIRED TO |
| BE GFI/GFI PROTECTED. 210.8B5 |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| |
| |