2009-12-16 14:11:40 | |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1. |
| |
| THIS PLAN IS BEING PASSED TO FACILITATE THE START OF |
| THIS PROJECT, THE PLANS HOWEVER ARE DEFICIENT, AND THE |
| FOLLOWING ITEMS NEED CORRECTING: |
| |
| COMMENTS RELATING TO SHEET E-3 |
| |
| 1} THE SMOKE ALARMS ARE SHOWN ON CIRCUIT A-29 WHICH IS |
| LABELED AS AHU-3 IN THE PANEL SCHEDULE. NOTE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED PER |
| 313.2.1 TO EXISTING ALARMS AS WELL. CIRCUIT B-26 IS |
| LABELED SMOKE DETECTOR. |
| |
| 2} CIRCUIT B-15 MUST BE A SMALL APPLIANCE CIRCUIT PER |
| 210.52(B)(1) "RECEPTACLE OUTLETS SERVED IN THE KITCHEN, |
| PANTRY, BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF |
| A DWELLING UNIT, THE TWO OR MORE 20-AMPERE |
| SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY |
| 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE |
| OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS |
| COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR |
| REFRIGERATION EQUIPMENT." THE CIRCUIT IS LISTED AS 20 |
| AMP IN THE PANEL SCHEDULE, BUT IS LABELED AS " GENERAL |
| USE".TO AVOID CONFUSION IN THE FIELD CHANGE TO |
| BREAKFAST ROOM OR SMALL APPLIANCE.ALSO ONE RECEPTACLE |
| ON THAT CIRCUIT IS IN THE KITCHEN WHICH IS NOT A |
| VIOLATION AS LONG AS IT IS SMALL APPLIANCE. |
| |
| 3} THE TRASH COMPACTOR SHOWN ON SHEET A401 IS NOT |
| CIRCUITED IN THE ISLAND AND IS NOT LISTED IN THE PANEL |
| SCHEDULE OR THE LOAD CALCULATION. CORRELATE SAME. |
| |
| COMMENTS RELATING TO SHEET E-5:ELECTRICAL RISER |
| DIAGRAM. |
| |
| 3} THE #4 CU GROUND RAN WITH THE FEEDERS FROM THE METER |
| TO THE FIRST MEANS OF DICONNECT (PANEL "A") CREATES A |
| PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE |
| REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE |
| TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| 250.24 (A)(5) |
| |
| 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THIS IS |
| BEING ASED FOR DUE TO RELOCATION OF THE SERVICE. |
| |
| 5} AN INTERSYSTEM BONDING TERMINAL PER 250.94 WILL BE |
| REQUIRED AT THE RELOCATED SERVICE. |
| |
| PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS |
| PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION. THE |
| REVIEWED PLAN MUST BE ON THE JOB SITE AT TIME OF |
| INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR |
| PLAN REVIEW. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |