 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.
  
 THIS PLAN IS BEING PASSED TO FACILITATE THE START OF
 THIS PROJECT, THE PLANS HOWEVER ARE DEFICIENT, AND THE
 FOLLOWING ITEMS NEED CORRECTING:
  
 COMMENTS RELATING TO SHEET E-3
  
 1} THE SMOKE ALARMS ARE SHOWN ON CIRCUIT A-29 WHICH IS
 LABELED AS AHU-3 IN THE PANEL SCHEDULE. NOTE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED PER
 313.2.1 TO EXISTING ALARMS AS WELL. CIRCUIT B-26 IS
 LABELED SMOKE DETECTOR.
  
 2} CIRCUIT B-15 MUST BE A SMALL APPLIANCE CIRCUIT PER
 210.52(B)(1) "RECEPTACLE OUTLETS SERVED IN THE KITCHEN,
 PANTRY, BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF
 A DWELLING UNIT, THE TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS
 COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT." THE CIRCUIT IS LISTED AS 20
 AMP IN THE PANEL SCHEDULE, BUT IS LABELED AS " GENERAL
 USE".TO AVOID CONFUSION IN THE FIELD CHANGE TO
 BREAKFAST ROOM OR SMALL APPLIANCE.ALSO ONE RECEPTACLE
 ON THAT CIRCUIT IS IN THE KITCHEN WHICH IS NOT A
 VIOLATION AS LONG AS IT IS SMALL APPLIANCE.
  
 3} THE TRASH COMPACTOR SHOWN ON SHEET A401 IS NOT
 CIRCUITED IN THE ISLAND AND IS NOT LISTED IN THE PANEL
 SCHEDULE OR THE LOAD CALCULATION. CORRELATE SAME.
  
 COMMENTS RELATING TO SHEET E-5:ELECTRICAL RISER
 DIAGRAM.
  
 3} THE #4 CU GROUND RAN WITH THE FEEDERS FROM THE METER
 TO THE FIRST MEANS OF DICONNECT (PANEL "A") CREATES A
 PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE
 TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6.
 250.24 (A)(5)
  
 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THIS IS
 BEING ASED FOR DUE TO RELOCATION OF THE SERVICE.
  
 5} AN INTERSYSTEM BONDING TERMINAL PER 250.94 WILL BE
 REQUIRED AT THE RELOCATED SERVICE.
  
 PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS
 PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION. THE
 REVIEWED PLAN MUST BE ON THE JOB SITE AT TIME OF
 INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR
 PLAN REVIEW.
  