2009-12-16 15:20:34 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| ***NOTE: PLEASE MAKE SURE ALL THE INFORMATION IS |
| PROVIDED AND FORM IS PROPERLY SIGNED AND DATED BY THE |
| REQUIRED PARTIES. |
| |
| 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF CLAY TILE. NOA 06-1213.03 SUBMITTED FOR THE |
| MISSION CLAY TILE EXPIRED ON 05/20/09. NEED TO PROVIDE |
| CURRENT NOA. |
| |
| B) ROOF TILE ADHESIVE. SEE CLAY TILE PRODUCT APPROVAL |
| FOR LISTED ADHESIVES. |
| |
| C) FLAT ROOF NOA 07-0730.03. PROVIDE RAS 117 |
| CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE |
| OF NOA. |
| C(1) SPECIFY WHICH APPROVED ASSEMBLY AND BASE SHEET |
| FASTENING OPTION IS GOING TO BE USED FROM NOA |
| SUBMITTED. |
| |
| 3- OWES $4117.68 WHICH IS THE BALANCE FOR THE PERMIT |
| FEE. |
| |
| 4- SHEET A301. REVISE STUCCO SPECIFICATIONS ON SECTIONS |
| THRU KITCHEN AND MASTER BATHROOM. TABLE R703.4 DOESN'T |
| APPLY TO STUCCO. SEE TABLE R702.1(1) AND REVISE STUCCO |
| THICKNESS AS REQUIRED. |
| ALSO, SPECIFY TWO LAYERS OF WATER-RESISTANT BARRIER AS |
| REQUIRED BY SEC. R703.6.3. |
| |
| 5- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| POLYCYNENE INSULATION TO BE USED TO VERIFY REQUIRED |
| THICKNESS AND COORDINATE WITH THE ENERGY CALCULATIONS. |
| |