2009-12-16 15:20:34RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
 ***NOTE: PLEASE MAKE SURE ALL THE INFORMATION IS
 PROVIDED AND FORM IS PROPERLY SIGNED AND DATED BY THE
 REQUIRED PARTIES.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF CLAY TILE. NOA 06-1213.03 SUBMITTED FOR THE
 MISSION CLAY TILE EXPIRED ON 05/20/09. NEED TO PROVIDE
 CURRENT NOA.
  
 B) ROOF TILE ADHESIVE. SEE CLAY TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
  
 C) FLAT ROOF NOA 07-0730.03. PROVIDE RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA.
 C(1) SPECIFY WHICH APPROVED ASSEMBLY AND BASE SHEET
 FASTENING OPTION IS GOING TO BE USED FROM NOA
 SUBMITTED.
  
 3- OWES $4117.68 WHICH IS THE BALANCE FOR THE PERMIT
 FEE.
  
 4- SHEET A301. REVISE STUCCO SPECIFICATIONS ON SECTIONS
 THRU KITCHEN AND MASTER BATHROOM. TABLE R703.4 DOESN'T
 APPLY TO STUCCO. SEE TABLE R702.1(1) AND REVISE STUCCO
 THICKNESS AS REQUIRED.
 ALSO, SPECIFY TWO LAYERS OF WATER-RESISTANT BARRIER AS
 REQUIRED BY SEC. R703.6.3.
  
 5- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 POLYCYNENE INSULATION TO BE USED TO VERIFY REQUIRED
 THICKNESS AND COORDINATE WITH THE ENERGY CALCULATIONS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER