Date |
Text |
2009-12-08 08:41:10 | DENIED |
| REFERENCE: |
| FBC-2004 FUEL GAS |
| |
| 1. SHT P1-103 GAS ISOMETRIC 2-1/2" GAS LINE REQUIRED TO |
| EACH GB1 @ 1300 MBH PER TABLE 402.4(2). |
| |
| 2. SHT P1-103 GAS ISOMETRIC. PLEASE VERIFY ALL CUT |
| SECTION MEASUREMENTS. THE REVISION DOES NOT SHOW A |
| LENGTH FROM THE BRANCH LINE FOR GWH1 TO THE 1 INCH |
| ELBOW TO THE OFFSET TO THE DRYER AND SHOWS 80 FEET FROM |
| THE ELBOW TO THE DROP AT THE DRYER AND NO DROP LENGTH |
| TO THE DRYER. THE LENGTHS APPEAR TO BE CORRECT ON THE |
| PREVIOUS REVISION, 74' - 22' & 10'. HAVE THESE LENGTHS |
| CHANGED? ALSO THE LENGTH TO THE GWH1 FROM THE GAS MAIN |
| TO THE DROP IS SHOWN AS 23 FEET BUT SCALES OUT TO ABOUT |
| 6 FEET MAX. PLEASE CLARIFY. |
| |
| 3. THE FIELD INSPECTOR HAS INFORMED ME THAT THE METER |
| LOCATION HAS CHANGED AS WELL AS THE PIPING TO THE DRYER |
| CHANGED TO RUN DOWN THE CORRIDOR. PLEASE VERIFY AND IF |
| SO THESE CHANGES SHALL BE INDICATED ON THE REVISION FOR |
| THE ISOMETRIC RISER DIAGRAM AND THE FLOOR PLAN. |
| SECTIONS 106.1.1 & 401.1. IF THE METER LOCATION HAS |
| CHANGED, THIS MAY LENGTHEN THE TOTAL DEVELOPED LENGTH |
| AND MAY CALL FOR INCREASED PIPE SIZES DEPENDING ON THE |
| DISTANCE TO THE MOST REMOTE APPLIANCE FROM THE METER. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |