2009-12-21 07:48:50 | DENIED |
| REFERENCE: |
| FBC-2007 PLUMBING |
| FBC-2007 BUILDING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| FBC-2007 EXISTING BLDG |
| FLORIDA STATUTES |
| FLORIDA ADMINISTRATIVE CODE |
| |
| 1. ALL SHEETS WITH G3 ARCHITECTURAL TITLE BLOCKS SHALL |
| HAVE THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF |
| AUTHORIZATION) IN THE TITLE BLOCK. FAC 61G1-14.004(2) & |
| FS 481.2055. |
| |
| 2. PER SECTION 401.1 A LEVEL OF ALTERATION SHALL BE |
| ELECTED. |
| |
| 3. SHT A2.0 ACCESSIBLE TOILET STALLS SHALL REQUIRE A |
| LAV. SECTION 11-4.17.3 & FIG 30E. |
| |
| 4. SHOW COMPLIANCE WITH THE FOLLOWING: |
| ___FOR DRINKING FOUNTAIN: |
| A. 11-4.15.3 SPOUT LOCATION/HEIGHT |
| B. 11-4/15/5 CLEARANCES & CLEAR FLOOR SPACE |
| C. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| DIFFICULTY BENDING OR STOOPING |
| ___FOR W/C'S: |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| ___FOR LAVS: |
| A. 11-4.19.3 CLEAR FLOOR SPACE |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| ___FOR BATHROOMS: |
| A. 11-4.22.3 TURNING AREA |
| |
| 5. SHT A5.0 PER SECTION 1210.2 WALLS WITHIN 2 FEET OF |
| THE W/C'S SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| SURFACE TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. PLEASE |
| CLARIFY HOW VINYL WALL COVERING WILL COMPLY. SUBMIT |
| MANUF. SPECIFICATIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |