Plan Review Notes
Plan Review Notes For Permit 09120061
Permit Number 09120061
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-23 13:43:53******DENIED*****
  
  
 1. THE SCOPE OF WORK IS PROJECTED IN SUITE 550 WHICH IS
 ADJACENT TO SUITE 800. IS THIS THE 5TH FLOOR OR THE 8TH
 FLOOR? PLEASE EXPLAIN.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 3. AS OF 12/31/08, THE 2007 FLORIDA FIRE PREVENTION
 CODE BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION
 AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 4. PLEASE DECLARE THE NEW OCCUPANCY TYPE/USAGE AND THE
 OCCUPANT LOAD BASED ON THAT OCCUPANCY TYPE.
  
 5. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFYING THE 75; TRAVEL
 DISTANCE.
  
 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW