Plan Review Notes
Plan Review Notes For Permit 09120061
Permit Number 09120061
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-15 13:49:37 
 ** DENIED
  
  
  
 1) NOTE: THE ARCHITECTURAL TITLE BLOCK IS MISSING THE
 REQUIRED FIRM LICENSE NUMBER. THIS IS ALSO KNOWN AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE FLORIDA
 STATUTES 481.219 WHICH REQUIRES THE FIRM LICENSE
 NUMBER. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 WHICH REQUIRES THE NUMBER TO BE ON THE
 TITLE BLOCK.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
  
 2) NOTE: THE FOLLOWING MINIMUM CODES ARE REQUIRED TO BE
 ON PLANS. SOME OF CODES LISTED ARE INCORRECT.
 PLANS INDICATE 2004 FBC ON E3, HOWEVER AS OF MARCH 1ST
 2009 THE STATE ADOPTED THE 2007 FBC W/ 2009
 SUPPLEMENTS.
 PLANS ALSO INDICATE A 2005 NFPA-101 ON E-3. THERE WAS A
 2003 NFPA-101 AND AS OF DECEMBER 31ST, 2008 THE STATE
 ADOPTED THE 2006 NFPA-101.
 THE PLANS INDICATE THE 2005 NFPA-70 ( NEC), HOWEVER AS
 OF OCTOBER 1ST, 2009 THE STATE ADOPTED THE 2008 NFPA-70
 ( NEC).
 THE ADOPTION OF NFPA CODES REFERENCED BY THE FLORIDA
 BUILDING CODE ADOPTION PROCESS AND BY THE STATE FIRE
 MARSHAL CAN BE FOUND IN FAC 69A-60.003,.004, 69A-3.012
 THE ARCHITECTURAL PLANS AND ELECTRICAL PLANS NEED TO
 CONTAIN THE FOLLOWING CODES WHICH ARE RELEVANT TO THE
 DESIGN.
  
 2007 FBC W/2009 SUPPLEMENTS. ( INCLUDING 2ND SET OF
 2009 SUPPLEMENTS).
 2008 NFPA-70
 2002 NFPA-72
 2006 NFPA-101
  
 POSSIBLE TO BE NOTED BY FIRE PLAN REVIEW:
 2006 NFPA-1
 2007 FLORIDA FIRE PREVENTION CODE
  
 3) NOTE: NOTE #1 ON SHEET E2 MENTIONS SOME SORT OF
 LIGHTING SWITCHING TO ALLEVIATE MORE LIGHTING BEING ON
 FOR ENERGY CODE COMPLIANCE. HOWEVER PLEASE PROVIDE
 DETAIL ON WHAT WILL TAKE PLACE OR HOW THIS DEVICE WILL
 ACHIEVE COMPLIANCE. HOW WILL LIGHTING BE AUTOMATED?
 WILL THE SWITCHING LOCATIONS BE ON THE LOAD SIDE OF THE
 OCCUPANCY SENSORS?
 13-415.AB.1.1, .1.2.
  
  
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  