Plan Review Notes
Plan Review Notes For Permit 09120061
Permit Number 09120061
Review Stop B
Sequence Number 1
Notes
Date Text
2009-12-16 13:01:32BUILDING PLAN REVIEW
 PERMIT: 09120061
 ADD: 222 LAKEVIEW SUITE# 550
 CONT: MIAMI SYSTEMS
 TEL: (561)394-5450
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DEC. 16/ 2009
  
  
 1) G3 ARCHITECTURE DESIGN & PLANNING HAS NOT PROVIDED
 THE REQUIRED CERTIFICATE OF AUTHORIZATION REQUIRED BY
 THE ARCHITECTURAL BOARD AND STATE ADMINISTRATIVE CODE,
 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. ADD
 THE NUMBER TO EACH SHEET.
  
 2) SHEET A0.1:
 2A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2B) PROJECT DATA: TYPE OF BUILDING DECLARED IS A TYPE
 I-B PLEASE SEE THIS BUILDING IS OVER 12 STORIES IN
 HEIGHT REQUIRING IT TO BE A TYPE I-A BUILDING , SEE
 TABLE 503.
  
 2C) PROJECT DATA INDICATES THE USE GROUP AS A A-2UNDER
 THE IBC, PLEASE SEE FLORIDA BUILDING CODE SECTION 303
 A-3 (GYMNASIUMS WITHOUT SPECTATOR SEATING).
  
 2D) PROJECT DATA INDICATES THE OCCUPANT LOAD OF 30 AND
 FACTOR OF 1/100, PLEASE REVIEW TABLE 1004.1.1 FOR
 EXERCISE ROOM WITH EQUIPMENT 50 GROSS AND LOCKER ROOMS
 50 GROSS, PLEASE MAKE CORRECTIONS.
  
 2E) PROJECT DATA, DOES NOT INDICATE IF THE HI-RISE IS
 SPRINKLED OR NOT?
  
  
 3) SHEET A2.0;
 3A) PLANS INDICATE ONLY ONE EXIT, PLEASE REVIEW TABLE
 1015.1 FOR A OCCUPANCIES WITH OCCUPANT LOADS GREATER
 THAN 49 TWO EXITS WILL BE REQUIRED.
  
 3B) THE DRINKING FOUNTAIN NITCH DOES NOT INDICATE THE
 WIDTH OF THE NITCH FIGURE 27. PLEASE ALSO PROVIDE THE
 CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN ON SHEET
 A6.0. 11-4.15.5 CLEARANCES.
  
 3C) ROOM 014 AND DOOR# 14 APPEARS TO BE MISSING THE
 18??? MANEUVERING DISTANCE ON THE LATCH SIDE. 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITHIN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 3D) PLEASE SEE IN BOTH RESTROOMS WITHIN THE ENTRY AND
 THE TURNING AROUND OBSTRUCTIONS FIGURE 7B WHEN X< 48
 INCHES.
  
 3E) PLANS FAIL TO PROVIDE A LAVATORY WITHIN THE
 ACCESSIBLE TOILET STALL. ACCESSIBLE STALLS BOTH
 RESTROOMS, PLEASE SEE 912.8 OF THE EXISTING BUILDING
 CODE, CHANGE OF OCCUPANCY AND THE REQUIREMENTS FOR
 ACCESSIBILITY SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE. 11-4.1.6(1)(B) EXISTING
 ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED, THEN
 EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 11-4.1.1 TO SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR
 NEW CONSTRUCTION. IF THE APPLICABLE PROVISION FOR NEW
 CONSTRUCTION REQUIRES THAT AN ELEMENT, SPACE, OR COMMON
 AREA BE ON AN ACCESSIBLE ROUTE, THE ALTERED ELEMENT,
 SPACE.
  
 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES
 (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE
 ROUTE.
  
 4) PLANS ARE MISSING DOOR SCHEDULE INDICATING THE SIZE
 OF THE DOORS, 1008.1.1.
  
 5) SHEET A.6 FURNITURE PLAN, WITH THE LAY OUT OF THE
 FURNITURE PLAN IT IS APPARENT THAT WITH THE SINGLE EXIT
 COMMON PATH OF TRAVEL IS A ISSUE, SEE SECTION 1014.3
 (5)
 WHERE A TENANT SPACE IN GROUP A OCCUPANCY HAS AN
 OCCUPANT LOAD OF MORE THAN 50, THE LENGTH OF A COMMON
 PATH OF EGRESS TRAVEL SHALL NOT BE MORE THAN 20 FEET
 (6098 MM).
  
 6) SHEET A5 PLEASE PROVIDE THE SMOKE DEVELOPMENT AND
 FLAME SPREAD RATINGS PER SECTION 803.1 AND TABLE 803.5.
 FOR WALL FINISHES.
  
 7) NOTE PLANS DO NOT INDICATE ANY EXTERIOR WALL
 SECTIONS, INSULATION NOR THE HEIGHT OF GYPSUM ABOVE THE
 FINISH CEILING. PLEASE SEE COMMENT IF FOAM INSULATION
 IS TO BE USED AS THE EXTERIOR
 WALL INSULATION. MECHANICAL CODE 602.2.1.5.1-
 PLENUMS!!!
  
 602.2.1.5 FOAM PLASTIC INSULATION. FOAM PLASTIC
 INSULATION USED AS WALL OR CEILING FINISH IN PLENUMS
 SHALL EXHIBIT A FLAME SPREAD INDEX OF 75 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF 450 OR LESS WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84 AND SHALL ALSO COMPLY WITH
 SECTION 602.2.1.5.1, 602.2.1.5.2 OR 602.2.1.5.3.
  
 602.2.1.5.1 SEPARATION REQUIRED. THE FOAM PLASTIC
 INSULATION SHALL BE SEPARATED FROM THE PLENUM BY A
 THERMAL BARRIER COMPLYING WITH SECTION 2603.4 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 8) CHANGE IN OCCUPANCY: BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  