Plan Review Notes
Plan Review Notes For Permit 09120046
Permit Number 09120046
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2010-01-27 08:27:211. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 2. THE EXISTING RATED SHAFT AND ORIGINAL GREASE DUCT
 DISPLAYED ON SHEET 3.3.M IS TO BE FIELD VERIFIED AND
 INSPECTED BY MECHANICAL INSPECTORS. ANY VIOLATIONS OF
 CODE DISCOVERED WILL NEED TO BE CORRECTED BY SUBMITTING
 PLANS AND PERMITS.
  
 3. NO FIRE SPRINKLER PLANS PROVIDED. PLEASE SUPPLY
 COMPLETE FIRE SPRINKLER PLANS ILLUSTRATING DESIGN, HEAD
 LOCATION, WATER SUPPLY, FIRE DEPARTMENT CONNECTION,
 VALVES AND ALL OTHER APPURTENANCES. SEPARATE SHOP
 DRAWINGS WILL BE REQUIRED PRIOR TO ANY INSTALLATION.
  
 4. ON PAGE 2.1E ONLY ONE HORN STROBE IS SHOWN IN THE
 LOUNGE PROPER. ANOTHER ONE IS DISPLAYED IN THE MAIN
 LOBBY OF THE BUILDING. ADDITIONAL HORN STROBES APPEAR
 TO BE NEEDED. CONFLICTS EXIST BETWEEN THE FIRE ALARM
 PLAN AND THE ELECTRICAL SHEETS. SEPARATE PLANS AND
 PERMITS REQUIRED FOR THE FIRE ALARM SYSTEM SHALL BE UL
 FOR CENTRAL STATION SERVICE.
  
 5. ON THE FIRE ALARM PLANS IT INDICATES THAT THAT AN
 ALARM, SUPERVISORY AND TROUBLE SIGNALS. A WATERFLOW
 SIGNAL IS ALSO REQUIRED TO BE SENT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION