2010-01-27 08:27:21 | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD, | | DUCT, AND FIRE SUPPRESSION SYSTEMS. | | | | 2. THE EXISTING RATED SHAFT AND ORIGINAL GREASE DUCT | | DISPLAYED ON SHEET 3.3.M IS TO BE FIELD VERIFIED AND | | INSPECTED BY MECHANICAL INSPECTORS. ANY VIOLATIONS OF | | CODE DISCOVERED WILL NEED TO BE CORRECTED BY SUBMITTING | | PLANS AND PERMITS. | | | | 3. NO FIRE SPRINKLER PLANS PROVIDED. PLEASE SUPPLY | | COMPLETE FIRE SPRINKLER PLANS ILLUSTRATING DESIGN, HEAD | | LOCATION, WATER SUPPLY, FIRE DEPARTMENT CONNECTION, | | VALVES AND ALL OTHER APPURTENANCES. SEPARATE SHOP | | DRAWINGS WILL BE REQUIRED PRIOR TO ANY INSTALLATION. | | | | 4. ON PAGE 2.1E ONLY ONE HORN STROBE IS SHOWN IN THE | | LOUNGE PROPER. ANOTHER ONE IS DISPLAYED IN THE MAIN | | LOBBY OF THE BUILDING. ADDITIONAL HORN STROBES APPEAR | | TO BE NEEDED. CONFLICTS EXIST BETWEEN THE FIRE ALARM | | PLAN AND THE ELECTRICAL SHEETS. SEPARATE PLANS AND | | PERMITS REQUIRED FOR THE FIRE ALARM SYSTEM SHALL BE UL | | FOR CENTRAL STATION SERVICE. | | | | 5. ON THE FIRE ALARM PLANS IT INDICATES THAT THAT AN | | ALARM, SUPERVISORY AND TROUBLE SIGNALS. A WATERFLOW | | SIGNAL IS ALSO REQUIRED TO BE SENT. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|