Plan Review Notes
Plan Review Notes For Permit 09120046
Permit Number 09120046
Review Stop E
Sequence Number 2
Notes
Date Text
2010-01-13 17:14:42 
 ** PROVISO *
 ** FAILURE TO ADDRESS COMMENTS BEFORE INSPECTIONS AS
 NOTED MAY RESULT IN ADDITIONAL FEES.
  
 NOTE #1 BEFORE ROUGH
 NOTE #2 BEFORE FINAL
 NOTE #3 BEFORE ROUGH
 NOTE #4 BEFORE FINAL
 NOTE #5 *REDLINED*
  
  
 1) NOTE: PLEASE MAKE THE CONTROL OF CORRIDOR LIGHTING
 CLEAR ON PLANS. PLANS INDICATE THE LIGHTS BEING
 CIRCUITED TO BREAKER HOWEVER NO CONTROLS. IF THESE ARE
 NIGHT LIGHTS ON 24/7 PLEASE INDICATE.
 13-415.AB.1.1, .1.2.
 PER DESIGNER AND PLANS ALL LIGHTING FOR THE MOST PART
 WILL BE CONTROLLED BY OCCUPANCY SENSORS. HOWEVER THE
 PLANS STILL INDICATE A KEYPAD AT KITCHEN DOOR AREA. THE
 RISER ALSO STILL INDICATES A LIGHTING CONTROL PANEL
 WHICH THERE IS NO DETAILS FOR.
 PLEASE PROVIDE DETAIL ON PLANS FOR OCCUPANCY SENSORS
 AND MASTER OFF CONTROLS ARE FRONT DOOR. PLEASE ALSO
 PROVIDE FOR TYPICAL CONTROLS/WIRING METHOD. A DETAIL
 BOX ON THESE WOULD BE SUFFICIENT. TYPICAL DETAILS CAN
 BE FOUND ON MOST LIGHTING CONTROL MANUFACTURE WEBSITES.
 NO LIGHTING OR CONTROLS SHOWN ON PLANS FOR WALK-IN
 COOLER AND OTHER ARE OFF WALK IN COOLER AREA. PLANS ARE
 TO BE REVISED TO SHOW. THE COOLER IT SELF WILL BE UNDER
 SEPARATE PERMIT.
  
 2) NOTE: PLEASE PROVIDE FIXTURE LEGEND OF SPECIFIC
 FIXTURES ONCE KNOWN FOR FINAL RECORD PLANS.
 REVISE PERFORMANCE CALCULATIONS IF WATTAGE
 INCREASES.13-415.AB.5.
  
 3) NOTE: ALL DEVICES FOR HORN, STROBES DEVICES FOR ADA
 COMPLIANCE SHALL BE SHOWN ON FA PERMIT. PLANS NOW
 INDICATE CANDELA LEVEL HOWEVER NO OTHER DETAILS FOR
 HEIGHTS, DB LEVELS ETC.
 FBC 11-4.28.1,.2 AND .3.
  
 4) NOTE: PANEL SCHEDULES TO BE REVISED FOR SPECIFIC
 CIRCUITS TO ALL ROOMS AND AREAS IN WHICH THEY FEED.
 EXAMPLE: LIGHTING FRONT, LIGHTING OFFICES/KITCHEN AREA
 ETC.
 408.4
  
 5) NOTE: PLANS INDICATE A 2008 EDITION OF NFPA-101
 HOWEVER THIS SHOULD BE 2006. THIS WAS REDLINED ON
 PLANS. ( FOR INFORMATION, 101 CODES ARE 2003, 2006 AND
 2009. THERE IS NO 2008 101. ( MISPRINT ON PLANS)
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  