2010-01-13 17:14:42 | |
| ** PROVISO * |
| ** FAILURE TO ADDRESS COMMENTS BEFORE INSPECTIONS AS |
| NOTED MAY RESULT IN ADDITIONAL FEES. |
| |
| NOTE #1 BEFORE ROUGH |
| NOTE #2 BEFORE FINAL |
| NOTE #3 BEFORE ROUGH |
| NOTE #4 BEFORE FINAL |
| NOTE #5 *REDLINED* |
| |
| |
| 1) NOTE: PLEASE MAKE THE CONTROL OF CORRIDOR LIGHTING |
| CLEAR ON PLANS. PLANS INDICATE THE LIGHTS BEING |
| CIRCUITED TO BREAKER HOWEVER NO CONTROLS. IF THESE ARE |
| NIGHT LIGHTS ON 24/7 PLEASE INDICATE. |
| 13-415.AB.1.1, .1.2. |
| PER DESIGNER AND PLANS ALL LIGHTING FOR THE MOST PART |
| WILL BE CONTROLLED BY OCCUPANCY SENSORS. HOWEVER THE |
| PLANS STILL INDICATE A KEYPAD AT KITCHEN DOOR AREA. THE |
| RISER ALSO STILL INDICATES A LIGHTING CONTROL PANEL |
| WHICH THERE IS NO DETAILS FOR. |
| PLEASE PROVIDE DETAIL ON PLANS FOR OCCUPANCY SENSORS |
| AND MASTER OFF CONTROLS ARE FRONT DOOR. PLEASE ALSO |
| PROVIDE FOR TYPICAL CONTROLS/WIRING METHOD. A DETAIL |
| BOX ON THESE WOULD BE SUFFICIENT. TYPICAL DETAILS CAN |
| BE FOUND ON MOST LIGHTING CONTROL MANUFACTURE WEBSITES. |
| NO LIGHTING OR CONTROLS SHOWN ON PLANS FOR WALK-IN |
| COOLER AND OTHER ARE OFF WALK IN COOLER AREA. PLANS ARE |
| TO BE REVISED TO SHOW. THE COOLER IT SELF WILL BE UNDER |
| SEPARATE PERMIT. |
| |
| 2) NOTE: PLEASE PROVIDE FIXTURE LEGEND OF SPECIFIC |
| FIXTURES ONCE KNOWN FOR FINAL RECORD PLANS. |
| REVISE PERFORMANCE CALCULATIONS IF WATTAGE |
| INCREASES.13-415.AB.5. |
| |
| 3) NOTE: ALL DEVICES FOR HORN, STROBES DEVICES FOR ADA |
| COMPLIANCE SHALL BE SHOWN ON FA PERMIT. PLANS NOW |
| INDICATE CANDELA LEVEL HOWEVER NO OTHER DETAILS FOR |
| HEIGHTS, DB LEVELS ETC. |
| FBC 11-4.28.1,.2 AND .3. |
| |
| 4) NOTE: PANEL SCHEDULES TO BE REVISED FOR SPECIFIC |
| CIRCUITS TO ALL ROOMS AND AREAS IN WHICH THEY FEED. |
| EXAMPLE: LIGHTING FRONT, LIGHTING OFFICES/KITCHEN AREA |
| ETC. |
| 408.4 |
| |
| 5) NOTE: PLANS INDICATE A 2008 EDITION OF NFPA-101 |
| HOWEVER THIS SHOULD BE 2006. THIS WAS REDLINED ON |
| PLANS. ( FOR INFORMATION, 101 CODES ARE 2003, 2006 AND |
| 2009. THERE IS NO 2008 101. ( MISPRINT ON PLANS) |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |