Plan Review Notes
Plan Review Notes For Permit 09120046
Permit Number 09120046
Review Stop P
Sequence Number 1
Notes
Date Text
2009-12-10 18:08:35DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHT 1.1A FLOOR PLAN DOES NOT REFLECT THE EQUIPMENT
 SCHEDULE FOR ITEM #4. PLEASE CORRELATE. FLOOR PLAN
 SHOWS A 3 COMPARTMENT SINK BUT THE EQUIP. SCHED
 INDICATES A DISHTABLE STRAIGHT WITH NO WATER SUPPLY NOR
 DOES IT INDICATE A DRAIN. PLEASE CLARIFY. SECTIONS
 106.1.1, 601.1, 701.1 & 801.1.
  
 2. SHT 1.1A FLOOR PLAN SHOWS ITEM 2 AS A SINK, PRE-
 WASH OR GARBAGE DISPOSAL BUT THE EQUIPMENT SCHEDULE
 INDICATES IT AS A DISHTABLE STRAIGHT. PLEASE CLARIFY
 SECTION 106.1.1.
  
 3. SHT 1.1A ITEMS 6 & 23 DO NOT INDICATE WATER SUPPLIES
 OR DRAINAGE CONNECTION. PLEASE CLARIFY. SECTIONS
 106.1.1, 601.1 & 701.1.
  
 4. SHT 3.1M THE HAND SINKS IN THE FOOD PREP AREA SHALL
 CONNECT TO THE GREASE INTERCEPTOR. SECTION 1003.3.1.
 ITEM #2 MAY BE REQUIRED TO CONNECT TO THE GREASE SYSTEM
 AS WELL WHEN THE FIXTURE IS IDENTIFIED.
  
 5. SHT 3.1M IDENTIFY WHAT FIXTURE IS DRAINED INTO THE
 FLOOR SINK ACROSS FROM THE 6 BURNER GRILL. SECTIONS
 106.1.1 & 801.1.
  
 6. PER TABLE 1003.3.4.1 THE FLOW-THROUGH RATING FOR ALL
 FIXTURES SHALL BE INDICATED ON THE PLANS. SEE SECTIONS
 1003.3.4.1 & 1003.3.4.2.
  
 7. SHT 3.1M TRAPZILLA DETAIL. 2-WAY CLEANOUTS ARE
 REQUIRED ON THE INLET AND OUTLET PIPING. UTILITY
 STANDARD AND TRAPZILLA INSTALLATION INSTRUCTIONS.
  
 8. SHT 3.2M WATER RISER DIAGRAM. PER SECTION 604.9
 WATER HAMMER ARRESTORS ARE REQUIRED AT THE ICE MAKER &
 THE DISHWASHER. PER PDI-WH 201 AIR CHAMBERS ARE NOT
 APPROVED. PLEASE DELETE FROM RISER DIAGRAM.
  
 9. SHTS 3.1M & 3.2M SHOW DIFFERENT TRAPZILLA MODELS.
 THE TRAPZILLA MODEL TZ-600 SHOULD BE INSTALLED. SECTION
 1003.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved