2009-12-19 15:19:08 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. OUTSIDE AIR INTAKE FOR AHU 1, 2 IS FACING A STREET. |
| MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS |
| SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY |
| HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS STREETS, |
| ALLEYS, PARKING LOTS AND LOADING DOCKS IN ACCORDANCE |
| WITH FBC-M 401.4.1. |
| |
| 2. NO OUTSIDE AIR CALCULATIONS WERE PROVIDED. PROVIDE |
| VANTILATION CALCULATIONS FOR THE PROPOSED NEW OCCUPANCY |
| IN ACCORDANCE WITH FBC-EB 909.1 AND FBC-M SECTION 403. |
| |
| 3. AHU 1 AND AHU 2 ARE BOTH MARKED ON FLOOR PLANS AS |
| AHU 1. PLEASE CORRECT IN ACCORDANCE WITH FBC-M 304.11. |
| |
| 4. NO INFORMATION IS PROVIDED REGARDING THE LOCATION OF |
| NEW REMOTE CONDENSING UNITS. PROVIDE ROOF MECHANICAL |
| PLAN AND ENSURE THE REQUIREMENTS OF FBC-M 304.10 FOR |
| GUARDS AND FBC-M 306.5 FOR ACCESS HAVE BEEN MET. |
| |
| 5. PROVIDE COOLING LOAD CALCULATIONS FOR THE PROPOSED |
| NEW AC EQUIPMENT IN ACCORDANCE WITH FBC-B 13-407.AB.1. |
| |
| 6. PROVIDE PRODUCT APPROVAL FOR ANY PRE-ENGINEERED A/C |
| STANDS TO BE USED IN ACCORDANCE WITH FAC 9B-72. |
| |
| 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN |
| ACCORDANCE WITH FBC-M 307.2.1. |
| |
| 8. SHOW AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH |
| FBC-M 307.2.3. |
| |
| NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS REQUIRED |
| FOR EACH OF THE FOLLOWINGMECHANICAL SYSTEMS: COMMERCIAL |
| KITCHEN HOOD EXHAUST SYSTEM, HOOD SUPPRESSION SYSTEM |
| AND WALK-IN COOLER/FREEZER SYSTEM. |
| |