Plan Review Notes
Plan Review Notes For Permit 09120046
Permit Number 09120046
Review Stop M
Sequence Number 1
Notes
Date Text
2009-12-19 15:19:08REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OUTSIDE AIR INTAKE FOR AHU 1, 2 IS FACING A STREET.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS IN ACCORDANCE
 WITH FBC-M 401.4.1.
  
 2. NO OUTSIDE AIR CALCULATIONS WERE PROVIDED. PROVIDE
 VANTILATION CALCULATIONS FOR THE PROPOSED NEW OCCUPANCY
 IN ACCORDANCE WITH FBC-EB 909.1 AND FBC-M SECTION 403.
  
 3. AHU 1 AND AHU 2 ARE BOTH MARKED ON FLOOR PLANS AS
 AHU 1. PLEASE CORRECT IN ACCORDANCE WITH FBC-M 304.11.
  
 4. NO INFORMATION IS PROVIDED REGARDING THE LOCATION OF
 NEW REMOTE CONDENSING UNITS. PROVIDE ROOF MECHANICAL
 PLAN AND ENSURE THE REQUIREMENTS OF FBC-M 304.10 FOR
 GUARDS AND FBC-M 306.5 FOR ACCESS HAVE BEEN MET.
  
 5. PROVIDE COOLING LOAD CALCULATIONS FOR THE PROPOSED
 NEW AC EQUIPMENT IN ACCORDANCE WITH FBC-B 13-407.AB.1.
  
 6. PROVIDE PRODUCT APPROVAL FOR ANY PRE-ENGINEERED A/C
 STANDS TO BE USED IN ACCORDANCE WITH FAC 9B-72.
  
 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1.
  
 8. SHOW AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH
 FBC-M 307.2.3.
  
 NOTE: SEPARATE PLANS AND PERMIT APPLICATIONS REQUIRED
 FOR EACH OF THE FOLLOWINGMECHANICAL SYSTEMS: COMMERCIAL
 KITCHEN HOOD EXHAUST SYSTEM, HOOD SUPPRESSION SYSTEM
 AND WALK-IN COOLER/FREEZER SYSTEM.
  