Date |
Text |
2009-12-08 08:18:51 | |
| 1. DEADBOLT LOCKS NOTED ON DOOR SCHEDULE. DOORS THAT |
| ARE USED FOR EXITING CANNOT BE EQUIPPED WITH |
| DEAD-BOLTS. PLEASE PROVIDE MORE DETAILS. |
| |
| 2. SEPARATE PLANS AND PERMITS REQUIRED FOR HOOD, DUCT, |
| AND FIRE SUPPRESSION SYSTEMS. |
| |
| 3. NO EMERGENCY LIGHTING OR EXIT SIGNS DISPLAYED WITHIN |
| THE EXISTING EXIT CORRIDOR ON THE LIFE SAFETY PLAN. |
| |
| 4. IT APPEARS THAT ONE OF THE EXITS TERMINATES INTO THE |
| BUILDING'S COMMON AREA. NO INFORMATION PROVIDED RELATED |
| TO THE DOORS AND HARDWARE FROM THIS LOCATION. |
| |
| 5. THE OCCUPANT LOAD WILL BE ESTABLISHED BY THE BUREAU |
| OF FIRE PREVENTION. |
| |
| 6. DOES THE EXISTING BUILDING CONTAIN ANY FIRE ALARM |
| EQUIPMENT. NO FIRE ALARM EQUIPMENT IS SHOWN. |
| |
| 7. ON SHEET 2.0E, AN EMERGENCY LIGHT AND EXIT IS SHOWN |
| ABOVE A DOOR THAT SWINGS IN THE WRONG DIRECTION. |
| |
| 8. GAS INSTALLATIONS TO COMPLY WITH THE APPROPRIATE |
| NFPA STANDARDS. |
| |
| 9. PREVIOUSLY THIS SPACE WAS USED AS A BUSINESS |
| OCCUPANCY. THE SPACE THEN BECAME VACANT AND THE PLANS |
| ILLUSTRATE A CHANGE OF USE TO AN ASSEMBLY OCCUPANCY. |
| THE NEW PROPOSED USE IS REQUIRED TO COMPLY TO THE |
| REQUIREMENTS FOR NEW ASSEMBLY OCCUPANCIES. |
| |
| 10. MORE DETAILS REQUIRED ON THE EXISTING RATED HOOD |
| SHAFT ILLUSTRATED ON THE PLANS. |
| |
| 11. FLOOR PLAN DOES NOT ILLUSTRATE SEATING FOR |
| PHYSICALLY CHALLENGED INDIVIDUALS. |
| |
| 12. MORE DETAILS REQUIRED FOR THE COMMON AREA OF THE |
| BUILDING. PLEASE DESCRIBE INTERIOR FINISH, EXIT SIGNS, |
| EMERGENCY LIGHTS, AND ANY OTHER SAFETY RELATED |
| EQUIPMENT. |
| |
| 13. THE PLANS INDICATE THAT THE SPACE IS NOT FIRE |
| SPRINKLER PROTECTED. PLEASE BE ADVISED THAT "WHERE THE |
| OCCUPANT LOAD EXCEEDS 100, THE FOLLOWING ASSEMBLY |
| OCCUPANCIES SHALL BE PROTECTED THROUGHOUT BY AN |
| APPROVED SUPERVISED AUTOMATIC FIRE SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 9.7.1.1(1) |
| DANCE HALLS |
| DISCOTHEQUES |
| NIGHTCLUBS OR SIMILAR USAGE |
| ASSEMBLY OCCUPANCIES WITH FESTIVAL SEATING. |
| |
| DENIED |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| |