Plan Review Notes
Plan Review Notes For Permit 09120046
Permit Number 09120046
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-04 09:28:08 
 ** DENIED**
  
 1) NOTE: THE FOLLOWING CODES INDICATED ON THE SHEET ARE
 NOT ADOPTED BY THE STATE OF FLORIDA.
 PLANS LIST THE 2005 EDITION OF NFPA-70 ( NEC) HOWEVER
 THIS SHOULD BE 2008. THIS COULD HAVE BEEN REDLINED
 HOWEVER PLANS ARE COMING BACK FOR OTHER COMMENTS.
  
 ** SIDE NOTE** CODE SECTIONS REFLECTED ON PLANS ARE
 FROM THE 2004 FBC ON ELECTRICAL SHEETS.( ELECTRICAL
 NOTES)
  
 2) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK
 IS REQUIRED TO INCLUDE VALUE FOR THE FOLLOWING; DESIGN
 COST, ALL LABOR, ALL EQUIPMENT, ALL MATERIALS/BUILDING
 MATERIALS FOR ALL TRADES WHETHER OR NOT ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. VALUE APPLIED IS LOW.
 ** FBC 108.3
 ** ONCE APPROPRIATE VALUE IS ASSESSED THEN ADDITIONAL
 FEES WILL BE REQUIRED BEFORE PERMIT ISSUANCE.
  
 3) NOTE: RISER ONLY INDICATES ONE SET OF 3/0 AWG
 CONDUCTORS FOR FEEDERS AND SUB PANELS FOR 400AMPS.
 PLEASE SEE NEC 310.16 AS THESE ARE ONLY RATED FOR
 200AMPS. HOWEVER THE SERVICE SIZE BEING PROVIDED IS
 400AMPS.
 240.4, 310.16
  
 4) NOTE: THIS IS A CHANGE IN OCCUPANCY UNDER THE
 EXISTING BUILDING CODE CHAPTER 9. PLEASE SEE 13-101.3
 FOR CHANGES IN OCCUPANCY FOR ENERGY CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING ITEMS WHICH WERE NOT SHOWN ON
 PLANS FOR CODE COMPLIANCE OR OTHER ITEMS NOT SUBMITTED.
 MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE CHAPTER
 13 HAS NOT BEEN MET.
 PLEASE SEE THE 2007 FBC W/2009 SUPPLEMENTS INCLUDING
 SECOND SET OF 2009 SUPPLEMENTS ADOPTED BY THE STATE ON
 OCTOBER 1ST, 2009.
 ALONG WITH THE SHOWN METHOD B ON PLANS, A FIXTURE
 LEGEND WITH SPECIFIC FIXTURES NEEDS TO BE SHOWN TO
 REVIEW FOR MINIMUM CODE COMPLIANCE. SHOWING A 2X4
 FIXTURE WITH 2-32W BULBS DOES NOT GIVE THE ACTUAL
 ACCURATE WATTAGE/VA CONSUMPTION OF FIXTURE. PLEASE SEE
 13-415.AB.5 FOR INTERIOR ALLOWANCES AND APPENDIX FOR
 FIGURING.
  
 5) NOTE: PLEASE SUBMIT LIGHTING CONTROL INFORMATION,
 LEGEND, DETAILS TO MEET MINIMUM CODE COMPLIANCE FOR FBC
 13-415.AB.1.1,.1.2 AND .1.3.
 THERE IS NO CONTROLS SHOWN ON PLANS FOR LIGHTING.
 PLANS HAVE SOME SORT OF INDICATION FOR A LIGHTING
 CONTROL PANEL AND THE RISER SHOWS A LIGHTING CONTROL
 PANEL. HOWEVER NO INFORMATION OR DETAILS ARE SHOWN???
 PLANS DO NOT SHOW CONTROLS AS REQUIRED FOR THE OCCUPANT
 TO OVER RIDE ANY TIME OF DAY SCHEDULING.
 PLANS DO NOT SHOW CONTROLS IN LOCATIONS FOR THE
 OCCUPANT TO SEE *ALL* LIGHTING WHICH IS BEING
 OVERRIDDEN.
 PLANS NEED TO INDICATE ALL SEPARATE SPACE CONTROLS.(
 SHOWN IN OFFICE HOWEVER NOT OTHER AREAS)
  
 6) NOTE: IF THERE IS GOING TO BE ANY OUTSIDE LIGHTING
 PLEASE SEE 13-415.AB.1.4
  
 7) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 COORDINATE WITH PANEL SCHEDULES.408.4, 310.16, 240.4,
 220, GIVEN AS GENERAL SECTIONS BASED ON THE FACT LOAD
 CALCULATIONS, CIRCUITING AND SIXE OF OVER CURRENT
 PROTECTION DEVICES CAN NOT BE VERIFIED FOR CODE
 COMPLIANCE IF THE PLANS AND PANEL SCHEDULE DO NOT
 COORDINATE.
  
 EXAMPLE: PLEASE SEE SIGN J-BOX OUT FRONT FOR EXAMPLE
 WHICH INDICATES CIRCUIT A41- YET THE PANEL SCHEDULE IS
 BLANK. SEE 600.5 FOR MINIMUM VA REQUIRED TO BE
 ADDITIONAL SIGN CIRCUIT.
  
 EXAMPLE: PLEASE SEE ANOTHER EXAMPLE IS TO CIRCUIT
 EMERGENCY AND EXIT LIGHTS PER 700.12F. ( ONLY SOME
 SHOWN, HOWEVER SEE COMMENT BELOW)
  
 EXAMPLE: PLEASE SEE B37 IN CLOSET AREA, WHICH BY PANEL
 SCHEDULE THIS IS LABELED. *BAG IN BOX*?
  
 EXAMPLE: PLEASE SEE B16 WHICH IS NOT ON PLANS. THIS
 LIGHTING IS ALSO NOT SHOWN FOR LIGHTING CONTROLS PER
 NOTE #5 ABOVE.
  
 EXAMPLE: PLEASE SEE LIGHTING PLAN WHICH INDICATES B19
 ON PLAN AND PANEL SCHEDULE STATES BAR COOLER. HOW IS
 THIS ALSO A LIGHTING CIRCUIT?
  
 EXAMPLE: PLANS INDICATE CIRCUIT A-27 AT TWO COOLER DOOR
 LOCATIONS HOWEVER A-27/29 FEED THE EXHAUST HOOD.
  
 8) NOTE: PLEASE COORDINATE PLANS. THE REFLECTED CEILING
 PLANS AND THE LIFE SAFETY PLAN DOES NOT MATCH WITH THE
 ELECTRICAL LIGHTING PLANS. MOST OF THE EMERGENCY AND
 EXIT LIGHTS ARE IN DIFFERENT LOCATIONS.
 SEE REAR EXIT AND OTHER AREA FIXTURES. SOME ARE SHOWN
 AS EXIT/EMERGENCY LIGHTS AND THEN THE ELECTRICAL PLANS
 ONLY INDICATE THE SAME FIXTURES AS EXIT.
 PLEASE SEE 700.12F.
  
 9) NOTE: PLANS NEED TO COMPLETE BASE DESIGN FOR FIRE
 ALARM SYSTEM/DEVICES. ALL DEVICE LOCATIONS, HEIGHTS,
 LEVELS CANDELA AND DB RATINGS MUST BE SHOWN ON BASE
 PLANS FOR DESIGN INTENT. THE FIRE ALARM WILL BE
 REQUIRED UNDER SEPARATE PERMIT HOWEVER MINIMUM CODE
 COMPLIANCE DESIGN NEEDS TO BE SHOWN PER NFPA-72, FBC
 AND FS 633. SEE NEC 760 FOR CIRCUITING REQUIRED AS WELL
 AS NFPA 72 CHAPTER 4.
 ** THIS WILL NOT BE A PROVISO ITEM>
  
 10) NOTE: ELECTRICAL PLANS ONLY INDICATE THE LOCATION
 OF TWO OF THE PANELS WHEREAS THE LIFE SAFETY SHEET AND
 OTHER SHEETS INDICATE ALL THREE PANELS.
 110.26, 240.24
  
 11) NOTE: ALL LOW VOLTAGE SYSTEMS SUCH AS SOUND, CATV,
 PHONE ETC WILL BE UNDER SEPARATE PLANS AND PERMIT
 APPLICATION. THESE PLANS MAY NOT BE REFERENCED FOR ANY
 OF THESE ITEMS AS PLANS DO NOT SHOW COMPLETED SYSTEMS
 AT THIS TIME.
 ** NO SYMBOL LEGEND ON PLANS FOR ANY DEVICE WHICH MAY
 BE INCLUDED.
  
 12) NOTE: DETAIL FOR ELECTRICAL SYSTEMS UNDER HOOD AND
 PERTAINING TO HOOD FOR SHUT DOWN WILL ALSO BE REQUIRED
 UNDER SEPARATE PERMIT AND PLANS. ( NONE SHOWN AND HOOD
 IS UNDER SEPARATE PERMIT).
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  