Plan Review Notes
Plan Review Notes For Permit 09120037
Permit Number 09120037
Review Stop B
Sequence Number 1
Notes
Date Text
2009-12-02 13:13:08REROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
 SEC. 1609.4 FBC WITH 2009 REVISIONS. ENGINEER TO REVISE
 RAS 117 CALCULATIONS AND TAS 105 CALCULATIONS AS
 REQUIRED.
 ***NOTE: ENGINEER TO PROVIDE HIS NAME AND LICENSE # ON
 THE SIGNED SHEETS AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
  
 2- ENGINEER TAS 105 REPORT IS MISSING THE INFORMATION
 REGARDING THE SPECIFIC COMPONENT TO BE SECURED. NO
 COMPONENT WAS MARKED.
  
 3- ENGINEER TAS REPORT IS REFERENCING THE 2001 FBC. SEE
 TAS-105 STATISTICAL ANALYSIS PAGE AND UPDATE AS
 REQUIRED.
  
 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 5- ANY ROOF EQUIPMENT REQUIRES SEPARATE PERMIT FOR
 RE-INSTALLATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved