Plan Review Notes For Permit 09120037 |
Permit Number |
09120037 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-02 13:13:08 | REROOF BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". | | SEC. 1609.4 FBC WITH 2009 REVISIONS. ENGINEER TO REVISE | | RAS 117 CALCULATIONS AND TAS 105 CALCULATIONS AS | | REQUIRED. | | ***NOTE: ENGINEER TO PROVIDE HIS NAME AND LICENSE # ON | | THE SIGNED SHEETS AS REQUIRED BY CHAPTER 471 FLORIDA | | STATUTES. | | | | 2- ENGINEER TAS 105 REPORT IS MISSING THE INFORMATION | | REGARDING THE SPECIFIC COMPONENT TO BE SECURED. NO | | COMPONENT WAS MARKED. | | | | 3- ENGINEER TAS REPORT IS REFERENCING THE 2001 FBC. SEE | | TAS-105 STATISTICAL ANALYSIS PAGE AND UPDATE AS | | REQUIRED. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | 5- ANY ROOF EQUIPMENT REQUIRES SEPARATE PERMIT FOR | | RE-INSTALLATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|