Date |
Text |
2009-12-22 16:01:33 | DENIED |
| REFERENCE: |
| FBC-2007 FUEL GAS |
| FBC-2007 CHAPTER 1 |
| FLORIDA ADMINSITRATIVE CODE |
| FLORIDA STATUTES |
| |
| A. PLANS SUBMITTED INDICATE "COPIES FOR REFERENCE |
| ONLY". SHT P-4 GAS ISOMETRIC HAS BEEN SUBMITTED NOT FOR |
| REFERENCE BUT FOR PERMIT. IF THE DESIGN PROFESSIONAL IS |
| AN ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS |
| STATE REGULATING THE PRACTICE OF ENGINEERING AS |
| PROVIDED FOR IN CHAPTER 471, FLORIDA STATUTES THEN HE |
| OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE |
| AND DATE TO SAIN DRAWINGS. SECTION 106.1. THE SHEETS |
| SUBMITTED HAVE A TITLE BLOCK OF THE ENGINEER OF RECORD. |
| EITHER THE ENGINEER OF RECORD SHALL SIGN, SEAL & DATE |
| THE SHEETS SUBMITTED FOR PERMIT OR A NEW ENGINEER SHALL |
| SUBMIT THE REQUIRED GAS RISER DIAGRAM AND SIGN, SEAL |
| AND DATE SUCH PLANS. |
| |
| B. THE FOLLOWING INFORMATION IS REQUIRED FOR A GAS |
| PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| 2007 FUEL GAS CODE. -- THE ISOMETRIC SHALL SHOW ALL |
| PIPING TO THE METER IN ORDER TO DETERMINE THE REQUIRED |
| PIPE SIZE. |
| |
| 2. TYPE OF GAS, (LP OR NATURAL). |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 6. SHT P-4 GAS RISER DIAGRAM SHOWS 47,000 BTU ADDED FOR |
| THE OVEN, BUT MANUF. SHEETS SUBMITTED INDICATE THE BTU |
| LOAD TO BE 66,000. PLEASE CLARIFY. |
| |
| C. THE VALUATION OF THE PROJECT APPEARS TO BE LOW. SEE |
| BELOW FOR VALUATION REQUIREMENTS. |
| |
| 104.6.5 BUILDING PERMIT VALUATION. IF |
| IN THE OPINION OF THE BUILDING OFFICIAL |
| THE CLAIMED VALUATION OF BUILDING, AL- |
| TERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED ESTIMATES |
| AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| CLUDING LAND VALUE) TO MEET THE APPROVAL |
| OF THE BUILDING OFFICIAL. FOR PERMITTING |
| PURPOSES, VALUATION FOR BUILDINGS AND |
| SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| SWIFT OR THE SOUTHERN BUILDING CODE |
| CONGRESS INTERNATIONAL VALUATION TABLES, |
| LATEST EDITION, AND SHALL BE BASED ON |
| TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |