Plan Review Notes
Plan Review Notes For Permit 09120026
Permit Number 09120026
Review Stop G
Sequence Number 1
Notes
Date Text
2009-12-22 16:01:33DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
 FBC-2007 CHAPTER 1
 FLORIDA ADMINSITRATIVE CODE
 FLORIDA STATUTES
  
 A. PLANS SUBMITTED INDICATE "COPIES FOR REFERENCE
 ONLY". SHT P-4 GAS ISOMETRIC HAS BEEN SUBMITTED NOT FOR
 REFERENCE BUT FOR PERMIT. IF THE DESIGN PROFESSIONAL IS
 AN ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING THE PRACTICE OF ENGINEERING AS
 PROVIDED FOR IN CHAPTER 471, FLORIDA STATUTES THEN HE
 OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE
 AND DATE TO SAIN DRAWINGS. SECTION 106.1. THE SHEETS
 SUBMITTED HAVE A TITLE BLOCK OF THE ENGINEER OF RECORD.
 EITHER THE ENGINEER OF RECORD SHALL SIGN, SEAL & DATE
 THE SHEETS SUBMITTED FOR PERMIT OR A NEW ENGINEER SHALL
 SUBMIT THE REQUIRED GAS RISER DIAGRAM AND SIGN, SEAL
 AND DATE SUCH PLANS.
  
 B. THE FOLLOWING INFORMATION IS REQUIRED FOR A GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- THE ISOMETRIC SHALL SHOW ALL
 PIPING TO THE METER IN ORDER TO DETERMINE THE REQUIRED
 PIPE SIZE.
  
 2. TYPE OF GAS, (LP OR NATURAL).
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SHT P-4 GAS RISER DIAGRAM SHOWS 47,000 BTU ADDED FOR
 THE OVEN, BUT MANUF. SHEETS SUBMITTED INDICATE THE BTU
 LOAD TO BE 66,000. PLEASE CLARIFY.
  
 C. THE VALUATION OF THE PROJECT APPEARS TO BE LOW. SEE
 BELOW FOR VALUATION REQUIREMENTS.
  
 104.6.5 BUILDING PERMIT VALUATION. IF
 IN THE OPINION OF THE BUILDING OFFICIAL
 THE CLAIMED VALUATION OF BUILDING, AL-
 TERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED ESTIMATES
 AND/OR BONA FIDED SIGNED CONTRACTS (EX-
 CLUDING LAND VALUE) TO MEET THE APPROVAL
 OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION FOR BUILDINGS AND
 SYSTEMS SHALL BE FOUND IN MARSHALL AND
 SWIFT OR THE SOUTHERN BUILDING CODE
 CONGRESS INTERNATIONAL VALUATION TABLES,
 LATEST EDITION, AND SHALL BE BASED ON
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHAN-
 ICAL, INTERIOR FINISH, NORMAL SITE WORK
 (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, OVERHEAD
 AND PROFIT, EXCLUDING ONLY LAND VALUE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  