Plan Review Notes For Permit 09110608 |
Permit Number |
09110608 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-01 10:43:12 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | INSULATION NAIL ENHANCING AT PERIMETER AND CORNER AREAS | | AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF | | NOA 07-0822.10 SUBMITTED. SELECTED APPROVED ASSEMBLY | | NEEDS TO MEET THE DESIGN PRESSURES OF SEC. R301 OF 2007 | | FLORIDA RESIDENTIAL CODE. | | | | 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO SEC. | | R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA | | RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE | | "C". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|