2009-12-01 10:43:12RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 INSULATION NAIL ENHANCING AT PERIMETER AND CORNER AREAS
 AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA 07-0822.10 SUBMITTED. SELECTED APPROVED ASSEMBLY
 NEEDS TO MEET THE DESIGN PRESSURES OF SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO SEC.
 R301.2.1.4.3 OF 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C".
  