Plan Review Notes
Plan Review Notes For Permit 09110579
Permit Number 09110579
Review Stop E
Sequence Number 2
Notes
Date Text
2010-01-13 08:08:03** TEMP FAILED.
  
 1) NOTE: ELECTRICAL REVIEW IS OK AND VALUE HAS BEEN
 INCREASED FOR PROJECT. FEE BALANCE DUE BEFORE ISSUANCE.
  
 2) NOTE: THE INCORRECT NEC IS STATED ON PLANS. PLANS
 SHOW 2005 WHEN THESE SHOULD BE 2008. ALL PERMIT
 APPLICATIONS AFTER OCT 1ST, 2009 ARE UNDER THE 2008
 NEC. THIS CAN BE REDLINED AND STAMPED ON SHEETS WHICH
 ARE NOT BE CORRECTED FOR OTHER COMMENTS.
  
 3) NOTE: THERE ARE COMMENT FROM ZONING WHICH NEED TO BE
 ADDRESSED BEFORE PLANS CAN BE STAMPED. THE FIRST THREE
 SHEETS TO EACH SET CONTAINS MEASURMENTS AND SIZING NOT
 CONSISTENT WITHN ONE ANOTHER. ONE SET INDICATES ONE
 SIZE OR ELEVATION AND THE OTHER SET INDICATES A
 DIFFERENT SIZE OR ELEVATION.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717