Notes |
Date |
Text |
2009-12-10 11:20:16 | 2007 FBC W/2009 REVISIONS | | ADD 2ND FLOOR LOFT | | | | DENIED BY BUILDING | | | | 1) THE ENGINEER LISTED IN THE TITLE BLOCK OF THE PLANS | | IS REQUIRED TO SIGN AND SEAL THE DRAWINGS. FS 471 | | | | 2) PROVIDE DETAILS OF THE GUARDS THAT ARE REQUIRED AT | | THE OPENING FROM THE LOFT TO THE LIVING ROOM BELOW. | | SHOW THAT IT COMPLIES WITH THE REQUIREMENTS OF FBC | | R312. | | | | 3) THE ENERGY CALCULATION FORM IS NOT REQUIRED BECAUSE | | RENOVATION IS LESS THAN 30 % OF ASSESSED VALUE OF THE | | STRUCTURE. NOTE: THE 2007 ENERGY GLITCH AMENDMENTS NO | | LONGER ALLOW METHOD C. THEREFORE, FORM 1100C-07 IS NO | | LONGER ACCEPTABLE. 13-101.2 | | | | 4) THE FLOOR PLAN ON SHEET 1 OF THE DRAWINGS SHOWS THE | | LOFT IN RELATION TO THE EXISTING FIRST FLOOR BELOW. | | SUBMIT TWO DRAWINGS OF THE LOFT FLOOR PLAN WITH THE | | SECOND FLOOR ROOMS AND WALLS FOR CLARITY. | | | | 5) UPDATE THE ELECTRIC CODE EDITION TO REFERENCE THE | | 2008 NEC. | | | | 6) SMOKE ALARMS ARE REQUIRED TO COMPLY WITH THE 2007 | | FBC R313.2.1. | | | | 7) IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | COPY OF RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|