Plan Review Notes For Permit 09110551 |
Permit Number |
09110551 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-09 13:10:30 | ** DENIED ** | | | | ** REVIEW UNDER 2008 NEC. | | | | 1) NOTE: PLEASE PROVIDE COPY OF CONTRACT FOR ALL NEW | | ELECTRICAL AS SHOWN ON PLANS. THE VALUE FOR THE | | COMPLETE SCOPE OF WORK AS SHOWN IS LOW. FBC 108.3 | | REQUIRES THE VALUE TO INCLUDE ALL LABOR, EQUIPMENT, | | MATERIALS, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS | | ARE OWNER SUPPLIED. THIS INCLUDES CONCRETE WORK FOR | | DUCT BANK, AND ALL ELECTRICAL EQUIPMENT FOR CONTROLS | | ETC. | | | | 2) NOTE: PLEASE PROVIDE INFORMATION FOR WHICH PERMIT | | THE NEW GATES ARE GOING TO BE DONE. HAS THIS WORK BEEN | | APPLIED FOR? HAS THIS WORK ALREADY BEEN PERMITTED? | | | | 3) NOTE: MORE THAN ONE GROUND ROD MAY BE REQUIRED. | | BASED ON SOUTH FLORIDA SOIL CONDITIONS AT THIS LOCATION | | PLEASE SEE NEC 250.56 AND ADJUST PLANS. | | | | 4) NOTE: PLEASE SEE 2008 NEC 250.94 AND PROVIDE | | INTER-SYSTEM BOND. | | | | 5) NOTE: PLEASE IDENTIFY THE TERMINATION OF THE TAPPED | | CONDUCTORS ON THE LOAD SIDE OF THE TRANSFORMER. 240.21. | | THE TAPS ARE SHOWN TO PANEL PP HOWEVER NOT MAIN | | INDICATED? | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|