Plan Review Notes
Plan Review Notes For Permit 09110551
Permit Number 09110551
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-09 13:10:30** DENIED **
  
 ** REVIEW UNDER 2008 NEC.
  
 1) NOTE: PLEASE PROVIDE COPY OF CONTRACT FOR ALL NEW
 ELECTRICAL AS SHOWN ON PLANS. THE VALUE FOR THE
 COMPLETE SCOPE OF WORK AS SHOWN IS LOW. FBC 108.3
 REQUIRES THE VALUE TO INCLUDE ALL LABOR, EQUIPMENT,
 MATERIALS, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED. THIS INCLUDES CONCRETE WORK FOR
 DUCT BANK, AND ALL ELECTRICAL EQUIPMENT FOR CONTROLS
 ETC.
  
 2) NOTE: PLEASE PROVIDE INFORMATION FOR WHICH PERMIT
 THE NEW GATES ARE GOING TO BE DONE. HAS THIS WORK BEEN
 APPLIED FOR? HAS THIS WORK ALREADY BEEN PERMITTED?
  
 3) NOTE: MORE THAN ONE GROUND ROD MAY BE REQUIRED.
 BASED ON SOUTH FLORIDA SOIL CONDITIONS AT THIS LOCATION
 PLEASE SEE NEC 250.56 AND ADJUST PLANS.
  
 4) NOTE: PLEASE SEE 2008 NEC 250.94 AND PROVIDE
 INTER-SYSTEM BOND.
  
 5) NOTE: PLEASE IDENTIFY THE TERMINATION OF THE TAPPED
 CONDUCTORS ON THE LOAD SIDE OF THE TRANSFORMER. 240.21.
 THE TAPS ARE SHOWN TO PANEL PP HOWEVER NOT MAIN
 INDICATED?
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  