2010-01-21 11:59:36 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. THE DETAILS PROVIDED CONFLICT WITH THE NOA. FOR |
| INSTANCE, SHEET 3, SECTION A CIRCLED, CONFLICTS WITH |
| HAND DRAWN DETAILS. THE DESIGN PROPOSED IS NOT |
| SUPPORTED BY THE NOA. |
| |
| A. THE NOA DETAIL CIRCLED REQUIRES A MONOLITHIC SLAB, |
| FOOTERS WITH NO SLAB SHOWN ON THE SITE SPECIFIC |
| DRAWING. THE FOOTER DETAIL SITE SPECIFIC DRAWING |
| DIFFERS FROM THE NOA FOOTER DETAIL (SMALLER, DIFFERENT |
| REINORCEMENT). |
| B. HOW HAS IT BEEN DETERMINED THAT THE PROPOSED |
| IMPROVEMENT WILL RESIST WIND LOADS AND HAS THE EFFECT |
| ON THE EXISTING STRUCTURE BEEN ANALYZED? SEE SECTION A |
| ON THE NOA, THE SUBSTRATE REQUIRED FOR SUPPORT OF THE |
| CANOPY IS A CONCRETE TIE BEAM, BUT THE SITE SPECIFIC |
| PROPOSES TO USE A PARAPET WALL AS SUPPORT. C. ONLY TWO |
| DETAILS WERE CIRCLED ON THE NOA. PLEASE MARK ALL |
| PERTINENT DETAILS, CONNECTIONS, AND SPANS. IT IS |
| DIFFICULT TO DETERMINE CODE COMPLIANCE BASED ON |
| INFORMATION PROVIDED. FOR INSTANCE, IT APPEARS THAT THE |
| SPAN ALLOWED IS 6'9", NOT 9'6" AS PROPOSED, SEE BEAM |
| SCHEDULE MAXIMUM SPAN FOR A GIVEN TRIBUTARY WITH ON |
| SHEET 4. PLEASE MARK ON SHEETS 2,3,4, & 5 ALL PERTINENT |
| SPANS, SIZES, SPACING, ETC. |
| D. THE MANUFACTURER HAS SUGGESTED THAT, GIVEN THE SITE |
| CONDITIONS AND SPAN DESIRED, A FREESTANDING CANOPY |
| (WHICH CAN BE ATTACHED TO STRUCTURE ON ONE SIDE) COULD |
| BE CONSIDERED. |
| |
| 2. SEE NOTE 19 ON THE NOA, SITE SPECIFIC ENGINEERING |
| REQUIRED; NO DEVIATION FROM THE NOA ALLOWED WITHOUT |
| ENGINEERING. ALL DEVIATION FROM THE NOA WILL REQUIRE |
| CALCULATIONS. |
| |
| 3. THIS PERMIT WILL BE ISSUED WITH PROVISO - 3000 PSI |
| CONCRETE REQUIRED, MINIMUM SOIL BEARING PRESSURE 2000 |
| PSF (REQUIRED BY NOA). |
| |
| |