Plan Review Notes For Permit 09110430 |
Permit Number |
09110430 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-02 10:45:40 | REVISED M-101 DELTA 5, M-201 DELTA 4 | | | | NOTE: M-201 DETAIL F, FLOAT SWITCH MUST BE INSTALLED IN | | THE DRAIN PAN OR ON THE SECONDARY DRAIN OUTLET. THE | | FLOAT SWITCH MAY NOT BE INSTALLED IN THE PRIMARY DRAIN | | LINE UNLESS IT IS SUPPLEMENTAL TO THE FLOAT SWITCH | | INSTALLED IN ONE OF THE REQUIRED LOCATIONS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|