Plan Review Notes
Plan Review Notes For Permit 09110417
Permit Number 09110417
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-08 13:54:56 
 ** DENIED **
  
 1) NOTE: THIS IS A STORAGE OCCUPANCY WHICH DOES NOT
 ALLOW OTHER USE PER ZONING AND FLORIDA BUILDING CODE
 REQUIREMENTS.
 IF THE USE WERE ALLOWED THE BELOW COMMENTS WOULD STILL
 BE REQUIRED.
  
 2) NOTE: LIGHTING PERFORMANCE CALCULATIONS PER FBC
 13-415.AB.5, 13-400.B.0.4 ETC
 PLEASE ALSO SEE APPENDIX FOR TRACK LIGHTING
 CALCULATIONS.
  
 3) NOTE: LIGHTING CONTROLS PER FBC 13-415.AB.1.1,.1.2.
 THIS IS A BUILDING GREATER THAN 5K SQ FT. MAY NOT USE
 STANDARD SWITCHES.
  
 4) NOTE: EGRESS LIGHTING PER FBC 1016.2, NFPA-101
 7.8.1.3, 7.9.1.2, .2.2 REQUIRED FROM LOFT AREA.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  