Plan Review Notes For Permit 09110417 |
Permit Number |
09110417 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-08 13:54:56 | | | ** DENIED ** | | | | 1) NOTE: THIS IS A STORAGE OCCUPANCY WHICH DOES NOT | | ALLOW OTHER USE PER ZONING AND FLORIDA BUILDING CODE | | REQUIREMENTS. | | IF THE USE WERE ALLOWED THE BELOW COMMENTS WOULD STILL | | BE REQUIRED. | | | | 2) NOTE: LIGHTING PERFORMANCE CALCULATIONS PER FBC | | 13-415.AB.5, 13-400.B.0.4 ETC | | PLEASE ALSO SEE APPENDIX FOR TRACK LIGHTING | | CALCULATIONS. | | | | 3) NOTE: LIGHTING CONTROLS PER FBC 13-415.AB.1.1,.1.2. | | THIS IS A BUILDING GREATER THAN 5K SQ FT. MAY NOT USE | | STANDARD SWITCHES. | | | | 4) NOTE: EGRESS LIGHTING PER FBC 1016.2, NFPA-101 | | 7.8.1.3, 7.9.1.2, .2.2 REQUIRED FROM LOFT AREA. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|