Plan Review Notes For Permit 09110358 |
Permit Number |
09110358 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2010-05-18 17:56:00 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. AS DISCUSSED, PLEASE SPECIFY CONNECTORS, TOP AND | | BOTTOM. A SIMPSON PRODUCT APPROVAL FOR 22 DIFFERENT | | CONNECTORS WAS INCLUDED, BUT THE PLAN DOES NOT SPECIFY | | WHICH CONNECTOR IS PROPOSED. THE PLAN STATES THAT A | | SIMPSON POST BASE WAS USED AT THE BOTTOM, BUT THE | | PRODUCT APPROVAL SUBMITTED DOES NOT APPEAR TO INCLUDE A | | POST BASE. PLEASE REVISE THE DETAIL TO INCLUDE THE | | SPECIFIC PRODUCTS USED AND PROVIDE PRODUCT APPROVAL FOR | | THOSE PRODUCTS. | | | | PER JON VANDERBER'S EMAIL TO YANI - " . . . WE NEED TO | | SKETCH A LITTLE DIAGRAM OF THE 4 X 4 WITH THE WIND | | LOADS OF THE BRACKETS." WITHOUT THE BRACKET (CONNECTOR) | | INFORMATION, I CANNOT DETERMINE THAT THE CONNECTOR | | PROPOSED IS APPROVED BY THE MANUFACTURER/PRODUCT | | APPROVAL FOR THE APPLICATION PROPOSED, AND WIND UPLIFT | | INFORMATION IS SPECIFIC TO EACH CONNECTOR. | | | | | | | | | | | | | | | | |
|