Plan Review Notes
Plan Review Notes For Permit 09110350
Permit Number 09110350
Review Stop P
Sequence Number 1
Notes
Date Text
2009-12-08 14:37:12DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FBC-2004 EXISTING BUILDING
  
 1. THE APPLICATION FOR PERMIT REQUIRES THAT A CHANGE OF
 OCCUPANCY OR USE BE INDICATED OR IF NO CHANGE OF
 OCCUPANCY OR USE THAT SHALL BE INDICATED ALSO.
  
 2. SHT CVR PROJECT SCOPE INDICATES RENOVATION OF TENANT
 OFFICE SPACE. PLEASE CLARIFY, IS THIS AN EXISTING
 OFFICE SPACE?
  
 3. PER SECTION 401.4 A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THE EXISTING
 BUILDING CODE.
  
 4. PER SECTION 906.1 ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE IN OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5. SHTS A-1 & A-2 THE W/C AND LAV IN THE EXISTING
 BATHROOM SHALL COMPLY WITH SECTIONS 11-4.16 & 11-4.19
 WITH ALL SUBSECTIONS. PER SECTION 11-4.1.6(1)(B) IF
 EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE ALTERED,
 THEN EACH SUCH ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION
 11-4.1.1 TO SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR
 NEW CONSTRUCTION. (ALSO SEE COMMENT #1).
  
 6, PER SECTION 11-4.1.3 IF TOILET ROOMS ARE PROVIDED
 THEN EACH PUBLIC AND COMMON USE TOILET ROOM SHALL
 COMPLY WITH SECTION 11-4.22. SHOW COMPLIANCE FOR THE
 WATER CLOSET AND LAV IN ROOM 203 PER SECTIONS 11-4.16 &
 11-4.19 WITH ALL SUBSECTIONS.
  
 7. SHT A-2 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE (203)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved