Plan Review Notes
Plan Review Notes For Permit 09110337
Permit Number 09110337
Review Stop M
Sequence Number 2
Notes
Date Text
2009-12-23 16:39:09**PROVISO**
  
 1. PROVIDE MANUFACTURER'S DATA FOR SUPPLY AND EXHAUST
 FAN SHOWING EACH TO BE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12. CABLE TIES ON THE EXHAUST
 FAN ARE NOT A SUBSTITUTE FOR A WIND RESISTANT DESIGN OF
 THE APPLIANCE. THE SUPPLY FAN WIND LOAD REQUIREMENT WAS
 NOT ADDRESSED IN ANY WAY.
  
 2. NEW MECHANICAL EQUIPMENT ON THE ROOF IS SUBJECT TO
 SCREENING AND CONCEALMENT REQUIREMENTS OF THE PLANNING
 DEPARTMENT. FOR ADDITIONAL INFORMATION CONTACT ANA
 MARIA APONTE AT 561-822-1439.
  