Plan Review Notes For Permit 09110337 |
Permit Number |
09110337 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2009-12-23 16:39:09 | **PROVISO** | | | | 1. PROVIDE MANUFACTURER'S DATA FOR SUPPLY AND EXHAUST | | FAN SHOWING EACH TO BE DESIGNED FOR WIND RESISTANCE IN | | ACCORDANCE WITH FBC-M 301.12. CABLE TIES ON THE EXHAUST | | FAN ARE NOT A SUBSTITUTE FOR A WIND RESISTANT DESIGN OF | | THE APPLIANCE. THE SUPPLY FAN WIND LOAD REQUIREMENT WAS | | NOT ADDRESSED IN ANY WAY. | | | | 2. NEW MECHANICAL EQUIPMENT ON THE ROOF IS SUBJECT TO | | SCREENING AND CONCEALMENT REQUIREMENTS OF THE PLANNING | | DEPARTMENT. FOR ADDITIONAL INFORMATION CONTACT ANA | | MARIA APONTE AT 561-822-1439. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|