2010-03-17 09:14:12MARRIOTT HOME CARE
 2700 BROADWAY AVENUE
 PERMIT # 09110297
  
 1. "OUTSIDE STAIRS AND LANDINGS, OTHER THAN EXISTING
 OUTSIDE STAIRS AND LANDINGS, SHALL BE DESIGNED TO
 MINIMIZE WATER ACCUMULATIONS ON THEIR SURFACES" RE:
 FFPC SECTION 7.2..2.6.5
  
 2. "WHERE APPROVED BY THE AHJ, EXITS SHALL BE PERMITTED
 TO DISCHARGE TO ROOFS OR OTHER SECTIONS OF THE BUILDING
 OR AN ADJOINING BUILDING WHERE THE FOLLOWING CRITERIA
 ARE MET
  
 (A) THE ROOF / CEILING ASSEMBLY CONSTRUCTION HAS A FIRE
 RESISTANCE RATING NOT LESS THAN THAT REQUIRED FOR THE
 EXIT ENCLOSURE" RE: FFPC SECTION 7.7.6
  
 3. EMERGENCY LIGHTING IS REQUIRED PER FFPC SECTION
 7.9.1.2.
  
 4. "STAIR TREADS AND LANDINGS SHALL BE FREE OF
 PROJECTIONS OR LIPS THAT COULD TRIP STAIR USERS" RE:
 FFPC SECTION 7.2.2.3.3.2
  
 5. " GUARDS IN ACCORDANCE WITH 7.2.2.4 SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS THAT
 EXCEED 30 INCHES ABOVE THE FLOOR OR GRADE BELOW" RE:
 FFPC SECTION 7.2.2.4
  
 6. "OPEN GUARDS SHALL HAVE INTERMEDIATE RAILS OR AN
 ORNAMENTAL PATTERN SUCH THAT A SPHERE 4 IN. IN DIAMETER
 IS NOT ABLE TO PASS THROUGH ANY OPENING UP TO A HEIGHT
 OF 34 IN. AND THE FOLLOWING SHALL ALSO APPLY
  
 (A) THE TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD,
 AND BOTTOM ELEMENT OF A GUARDRAIL AT THE OPEN SIDE OF A
 STAIR SHALL BE SUCH SIZE THAT A SPHERE 6 IN. IN
 DIAMETER IS NOT ABLE TO PASS THROUGH THE TRIANGULAR
 OPENING". RE: FFPC SECTION 7.2.2.4.5.3
  
 7. NEW EXIT DOOR HARDWARE SHALL BE EQUIPPED WITH
 HARDWARE THAT DOES NOT REQUIRE THE USE OF A KEY, TOOL,
 SPECIAL KNOWLDEGE OR EFFORT FROM INSIDE THE BUILDING.
  
 8. EXIT SIGN AND EMERGENCY LIGHT REQUIRED OVER NEW EXIT
 DOOR.
  
 9. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 10. NEW STAIRS SHALL HAVE NO MORE THAN 12 FEET BETWEEN
 LANDINGS. RE: FFPC SECTION 7.2.2.2.1.1.A
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  