Plan Review Notes For Permit 09110297 |
Permit Number |
09110297 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-03-18 16:08:14 | 2007 FBC W/2009 REVISIONS | | NEW EXTERIOR EXIT STAIRWAY | | | | 1) THE COMPONENT AND CLADDING PRESSURES SPECIFIED FOR | | THE NEW EXTERIOR DOOR ARE TOO LOW. THE STRUCTURE IS | | LOCATED IN EXPOSURE CATEGORY 'C', THE MEAN ROOF HEIGHT | | IS APPROXIMATELY 24 FEET, THE EFFECTIVE WIND AREA IS 20 | | SQFT AND THE DOOR IS LOCATED IN WALL ZONE 5. PLEASE | | CORRECT. | | | | 2) THE PRODUCT APPROVALS FOR THE EXTERIOR DOOR SPECIFY | | THE DESIGN PRESSURES AS +/- 55 PSF FOR WATER INTRUSION. | | THIS DOOR MAY NOT BE ACCEPTABLE WHEN THE PRESSURES ARE | | CORRECTED. FBC 1714.5.2 | | | | 3) ACCESSIBLE HANDRAILS ARE REQUIRED ON EACH SIDE OF | | THE STAIRWAY AND SHALL COMPLY WITH FBC 1012 , 11-4.9.4 | | AND 11- 4.26.2 FOR HEIGHT, GRASPABILITY, EXTENSIONS, | | ETC. PROVIDE DETAILS THAT SHOW COMPLIANCE. | | | | 4) STAIR AND ELEVATED WALKWAY GUARDRAILS SHALL COMPLY | | WITH FBC 1013 FOR STRENGTH, HEIGHT AND OPENING | | LIMITATIONS. SHOW COMPLIANCE. | | | | 5) ADDRESS FIRE DEPARTMENT REVIEW COMMENTS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|