2010-03-18 16:08:142007 FBC W/2009 REVISIONS
 NEW EXTERIOR EXIT STAIRWAY
  
 1) THE COMPONENT AND CLADDING PRESSURES SPECIFIED FOR
 THE NEW EXTERIOR DOOR ARE TOO LOW. THE STRUCTURE IS
 LOCATED IN EXPOSURE CATEGORY 'C', THE MEAN ROOF HEIGHT
 IS APPROXIMATELY 24 FEET, THE EFFECTIVE WIND AREA IS 20
 SQFT AND THE DOOR IS LOCATED IN WALL ZONE 5. PLEASE
 CORRECT.
  
 2) THE PRODUCT APPROVALS FOR THE EXTERIOR DOOR SPECIFY
 THE DESIGN PRESSURES AS +/- 55 PSF FOR WATER INTRUSION.
 THIS DOOR MAY NOT BE ACCEPTABLE WHEN THE PRESSURES ARE
 CORRECTED. FBC 1714.5.2
  
 3) ACCESSIBLE HANDRAILS ARE REQUIRED ON EACH SIDE OF
 THE STAIRWAY AND SHALL COMPLY WITH FBC 1012 , 11-4.9.4
 AND 11- 4.26.2 FOR HEIGHT, GRASPABILITY, EXTENSIONS,
 ETC. PROVIDE DETAILS THAT SHOW COMPLIANCE.
  
 4) STAIR AND ELEVATED WALKWAY GUARDRAILS SHALL COMPLY
 WITH FBC 1013 FOR STRENGTH, HEIGHT AND OPENING
 LIMITATIONS. SHOW COMPLIANCE.
  
 5) ADDRESS FIRE DEPARTMENT REVIEW COMMENTS.
  