Plan Review Notes
Plan Review Notes For Permit 09110297
Permit Number 09110297
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-15 13:34:03 
 1. PLEASE INDICATE MAXIMUM OCCUPANT LOAD EXPECTED TO
 USE THE PROPOSED EXIT FACILITIES.
  
 2. PLEASE INDICATE THE CODE PROVISIONS THAT ALLOWS FOR
 THE USE OF A SHIPS LADDER FOR MEANS OF EGRESS IN A
 RESIDENTIAL BOARD AND CARE OCCUPANCY.
  
 3. THE TERMINUS OF THE SHIPS LADDER IS AN ENCLOSED
 COURT. THE ENCLOSED COURT CONTAINS WINDOWS AND DOORS ON
 EACH ELEVATION OF THE ENCLOSED COURT.
  
 4. PLEASE DESCRIBE EXIT FACILITIES FROM THE ENCLOSED
 COURT AREA.
  
 5. PLEASE INDICATE HOW THE EXIT ACCESS IS MAINTAINED ON
 THE FLAT ROOF AREA. HOW IS THIS MATERIAL SLIP RESISTANT
 AND MAINTAINED. PLEASE INDICATE CODE REFERENCES THAT
 ALLOWS FOR THE USE OF EXITING FROM THE ROOF AREA.
  
 6. PLEASE INDICATE HOW THE NEW HANDRAIL IS SECURED TO
 THE BUILDING.
  
 7. PLEASE INDICATE ANY WINDOW OR DOOR OPENINGS WITHIN
 TEN FEET OF THE FUTURE EXIT FROM THE ROOF.
  
 8. EXISTING VIOLATIONS EXIST WITHIN THE INTERIOR OF THE
 EXISTING SECOND FLOOR AREA.
  
 9. PLEASE INDICATE STAIR RISE, RUN, AND TREAD DEPTH OF
 THE PROPOSED STAIRS.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
 [email protected]