Plan Review Notes
Plan Review Notes For Permit 09110285
Permit Number 09110285
Review Stop P
Sequence Number 2
Notes
Date Text
2010-01-06 16:51:28 
  
 PASSED/PROVISO:
  
 SHT P1.01 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS. THE
 FLOOR PLAN SHOWS ONE BLDG DRAIN WITH A DOUBLE WYE
 PICKING UP BOTH TOILET ROOMS. BUT THE RISER SHOWS BOTH
 TOILET ROOMS EXITING THE BUILDING SEPARATELY. -- THE
 TRAPS FOR THE W/C'S ARE NOT APPROVED AS THE W/C'S HAVE
 INTEGRAL TRAPS AND DOUBLE TRAPING IS NOT APPROVED PER
 SECTION 1002.1. -- THE TRAPS FOR THE LAVS ARE INDICATED
 AS UNDER THE SLAB ON THE RISER DIAGRAM.
  
 SHT P1.01 THE WATER RISER DIAGRAM DOES NOT SHOW THE
 WATER SUPPLY TO EITHER W/C.
  
 A REVISION IS REQUIRED TO CORRECT THESE DIFICENCIES AND
 REFLECT THE INSTALLATION.
  
  
  
 1-14-10
 CHANGED TO FAILED STATUS BECAUSE 2ND SET OF PLANS IS
 MISSING SHEETS S1.01, THE ORIGINAL P1.01 PLUMBING PLAN,
 E1.01 & D1.01. WHEN TWO FULL SETS OF PLANS ARE
 SUBMITTED THEN THE STATUS WILL CHANGE.
  
  
  
  
  
 .