Plan Review Notes For Permit 09110285 |
Permit Number |
09110285 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-12-01 17:53:07 | DENIED | | REFERENCE: | | FBC-2007 PLUMBING | | FBC-2007 CHAPTER 1 | | | | 1. A SANITARY ISOMETRIC RISER DIAGRAM IS REQUIRED. | | SECTION 106.3.5.1.3(4)(6)(13). PLEASE SHOW ALL PIPE | | SIZES, TRAPS, VENTS ETC. SECTIONS 701.1, 901.1 & | | 1001.1. | | | | 2. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED. SECTION | | 106.3.5.1.3(3)(10(13). PLEASE SHOW ALL PIPE SIZES, | | VALVES AND (WHERE REQD BY SECTION 604.9) WATER HAMMER | | ARRESTORS. SECTION 601.1. | | | | 3. SHT G1.01 SCOPE OF WORK INDICATES "REMOVE & REPLACE | | KITCHEN CABINETS & APPLIANCES" WILL ANY OF THE | | APPLIANCES BE NEW APPLIANCES? IF YES WILL THERE BE ANY | | NEW GAS APPLIANCES? PLEASE CLARIFY. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|