2009-12-01 17:53:07DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. A SANITARY ISOMETRIC RISER DIAGRAM IS REQUIRED.
 SECTION 106.3.5.1.3(4)(6)(13). PLEASE SHOW ALL PIPE
 SIZES, TRAPS, VENTS ETC. SECTIONS 701.1, 901.1 &
 1001.1.
  
 2. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED. SECTION
 106.3.5.1.3(3)(10(13). PLEASE SHOW ALL PIPE SIZES,
 VALVES AND (WHERE REQD BY SECTION 604.9) WATER HAMMER
 ARRESTORS. SECTION 601.1.
  
 3. SHT G1.01 SCOPE OF WORK INDICATES "REMOVE & REPLACE
 KITCHEN CABINETS & APPLIANCES" WILL ANY OF THE
 APPLIANCES BE NEW APPLIANCES? IF YES WILL THERE BE ANY
 NEW GAS APPLIANCES? PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  