Plan Review Notes For Permit 09110276 |
Permit Number |
09110276 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-11-12 14:48:56 | RESIDENTIAL (R2) REROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- THIS IS A SINGLE FLAT ROOF. PARTIAL RE-ROOF IS NOT | | ALLOWED. NEED TO RE-ROOF ENTIRE ROOF. SEC. 611.1.1 OF | | 2007 FBC. | | | | 2- NOA 03-0501.02 SUBMITTED EXPIRED LAST YEAR ON | | 11/06/08. NEED TO PROVIDE CURRENT NOA. | | | | 3- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED TO MEET THE | | DESIGN PRESSURES OF SEC. 1609 FBC 2007. | | ***NOTES: A) IF GENERAL LIMITATION #7 ON NOA PROVIDE | | REQUIRES RAS 117 CALCULATIONS TO BE SIGNED AND SEALED, | | THEN SIGNED AND SEALED CALCULATIONS ARE REQUIRED. | | | | B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | REVISIONS TO THE 2007 FBC THIS BUILDING IS LOCATED ON | | EXPOSURE "C", NOT "B". | | | | 4) ROOF TOP EQUIPMENT REQUIRES SEPARATE PERMIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|