Plan Review Notes For Permit 09110267 |
Permit Number |
09110267 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-01-07 08:12:43 | PROVISO | | | | 1) NOTE: NO CHANGES OR INFORMATION SHOWN FOR EXTERIOR | | LIGHTING CONTROLS. MUST MEET 13-415.AB.1.4. IF | | EXISTING, STILL NEEDS TO MEET REQUIREMENTS GOING BACK | | EVEN FOR THE LAST 8 CODE CYCLES. ( | | PHOTO-SENSOR/TIME-CLOCK/ ASTRONOMICAL TIME CLOCK WITH | | PROGRAMMING BACK UP. | | MAY NOT BE BY BREAKER OR SP SWITCH ONLY. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | 561-805-6717 |
|