Plan Review Notes
Plan Review Notes For Permit 09110267
Permit Number 09110267
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-03 15:25:42 
 ** DENIED**
  
 1) NOTE: THE FOLLOWING CODES INDICATED ON THE SHEET ARE
 NOT ADOPTED BY THE STATE OF FLORIDA.
 PLANS LIST THE 2009 NFPA-101, HOWEVER THIS SHOULD BE
 2006. THIS COULD BE RED-LINED HOWEVER COMING BACK FOR
 OTHER COMMENTS.
 PLANS LIST A 2006 EDITION OF NFPA-70 ( NEC) HOWEVER
 THIS SHOULD BE 2008. FOR INFORMATION THERE WAS NOT A
 2006 NEC.
  
 2) NOTE: PLANS INDICATE NEW LIGHTING HOWEVER NO
 INFORMATION ON TYPE OF LIGHTS, HOW MANY LIGHTS, AND
 CONTROL OF LIGHTS ETC.
 13-415.AB.2 FOR EXTERIOR LIGHTING ALLOWANCES.
 13-415.AB.1.4 FOR TYPE OF CONTROL REQUIRED.
 NEC 310.16,240.4, 220.12, 220.42 FOR LOADS, CIRCUITING
 AND OVER CURRENT PROTECTION.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  